SMART-PULP
Smart Consistency Transmitter
13
Keystroke
ESC
[
⇓
]
ENTER
ENTER
[
⇓⇑
]
ENTER
ENTER
[
⇓
]
ENTER
[
⇓⇑
]
ENTER
ENTER
[
⇓
][
⇓
][
⇓
][
⇓
]
ENTER
[
⇓⇑
]
ENTER
ENTER
[
⇓
][
⇓
][
⇓
]
ENTER
[
⇓⇑
]
ENTER
ENTER
ESC
Disp.text
n.nn%Cs
MEASURE
CONFIGUR
LOWER RA
2.00%Cs
h.hh%Cs
SAVE OK?
LOWER RA
UPPER RA
5.00%Cs
h.hh%Cs
SAVE OK?
UPPER RA
MOUNTING
HOR TOP
desired
mounting
SAVE OK?
MOUNTING
BLADE TY
default
blade type
correct
blade type
SAVE OK?
BLADE TY
CONFIGUR
Description
Measured consistency
(start-up display).
To main menu.
The measurement menu.
To configuration menu.
————————————————-
Consistency (%) corresponding to 4 mA.
Default value 2.00% Cs.
Correct value.
————————————————-
Consistency (%) corresponding to 20 mA.
Default value 5.00% Cs.
Correct value.
————————————————-
Configuration of mounting position;
pipe orientation and transmitter’s
position on it.
Default value.
HORizontal TOP/SIDE
VERtical UP flow
————————————————
Sensor type check: sensor blade type
and material.
Should be the same as in installed
transmitter.
If type was not correct.
See the NOTE on the page 12.
————————————————
Back to main menu.
Keystroke
[
⇓
]
ENTER
ENTER
[
⇓⇑
]
ENTER
[
⇓⇑
]
ENTER
[
⇓⇑
]
ENTER
ENTER
ENTER
ENTER
ESC
ESC
ENTER
[
⇑⇑
]
ENTER
[
⇓
][
⇓
]
ENTER
ENTER
[
⇓
][
⇓
][
⇓
]
Disp.text
CONFIGUR
CALIBRAT
NEW RECI
RECIPE1
RECIPEn
ULIN
xxxxx
ASH0.0%
ASH0.0%
P1 1.000
P2 0.000
SAVE OK?
NEW RECI
CALIBRAT
MEASURE
x.xx%Cs
RECIPE1
RECIPEn'
SAVE OK?
NOT CALIB
x.xxx%Cs
Description
See the NOTE on the page 12.
E.g. recipe number 1 can be
accepted.
Default curve (unlinearized
shear force signal). 0-30 N =
0-100%. Recipe’s dominant
pulp type.
Give filler content (0.0% is
recommended if the laboratory
command is used).
Curve slope factor.
(Base curve = 1.0).
Curve offset (base curve = 0.0).
A3 can be performed for all
recipes.
Back to main menu.
Change active recipe to
measurement menu.
Active recipe which is to be
calibrated. If only one recipe
(e.g. 1), accept it.
Blinking warning for
uncalibrated recipe.
Consistency reading from base
curve. If correct, sampling and
laboratory analysis not required.
If base curve is not sufficient,
go to next Table and continue
from A6.
Most of the cases at least
single-point calibration is
needed to remove offset
between laboratory and
transmitter output.
Table 1.3a SMART-PULP Start-up calibration and configuration:
menu texts and keystrokes.
A1
A4
A5
A3
A2