- 56 -
◎
Calculation formula of heating target temperature
Pset (heating target temperature) =20
℃
+ (Target temperature compensation coefficient
÷
10) * (Heating compensation temperature point - current ambient temperature)
◎
The above different curves stands for the different value of Target temperature
compensation coefficient.
(When Target temperature compensation coefficient=1, the actual value is 0.1)
◎
The target temperature range of automatic temperature adjustment is 20-60
℃
Auxiliary Electric Heater for Water Tank
◎
Start conditions (all below conditions must be met at the same time)
1) In hot water mode;
2) The compressor runs for start time for electric heating of water tank
(
30
)
minutes;
3) There is a demand for hot water, and the temperature of the water tank is ≤55
℃
;
4) The pump is running
◎
Exit condition (only need to meet any one of the below conditions)
1) When the heat pump is performing cooling mode / hot water mode;
2) When there is no demand for hot water or constant temperature control;
3) The water tank temperature sensor has a fault alarm;
◎
When it is under defrosting / forced defrosting / secondary antifreeze , the electric heating is
forced to turn on;
Содержание V1 Series
Страница 9: ...8 V1 18 V1 23 V1 28 V1 35...
Страница 10: ...9 Exploded view V1 08...
Страница 11: ...10 V1 13...
Страница 12: ...11 V1 18 23...
Страница 13: ...12 V1 28 35...
Страница 16: ...15 Figure 2 Figure 3...
Страница 18: ...17 Figure 7 Figure 8...
Страница 20: ...19 Figure 11 Figure 12 Figure 13...
Страница 23: ...22 Electrical Wiring Diagram 1 Single phase system V1 08...
Страница 24: ...23 2 Three phase system V1 13 18 23...
Страница 25: ...24 3 Three phase system V1 28 35...