- 32 -
definition, range and default value.
◎
List of system parameters
Code
Definition
Settable Range
Default
P01
Temp difference of return water and
cooling target temp
2
℃
~18
℃
2
℃
P02
Temp difference of return water and hot
water target temp
2
℃
~18
℃
5
℃
P03
Hot water setting temp.
28
℃
~60
℃
50
℃
P04
Cooling setting temp.
7
℃
~30
℃
12
℃
P05
Heating setting temp.
15
℃
~50
℃
35
℃
P06
Setting temp of exhaust gas too high
protection (TP4)
50
℃
~125
℃
120
℃
P07
Setting temp of exhaust gas too high
recover (tp0)
50
℃
~125
℃
95
℃
P08
Water temp. compensation
-5
℃
~15
℃
(inlet/outlet water
& water tank)
P09
Defrosting frequency
30-120HZ
60HZ
P10
Defrosting period
20MIN~90MIN
45MIN
P11
Defrosting enter temp.
-15
℃
~-1
℃
-3
℃
P12
Defrosting time
5MIN~20MIN
10MIN
P13
Defrost exit temp.
1
℃
~40
℃
20
℃
P14
Defrosting environment and evaporator
coil temp. difference 1
0
℃
~15
℃
5
℃
P15
Defrosting environment and evaporator
coil temp. difference 2
0
℃
~15
℃
5
℃