- 55 -
User setting
High Temperature Antisepsis Function: (when hot water function is selected)
◎
High temperature Antisepsis cycle is once every 7 days
(
Cancel this function when the
selection is 0
)
;
◎
When entering the high temperature Antisepsis, the water tank electric heater will be
forced to turn on.
◎
During the Antisepsis process, if the water tank temperature > 60
℃
(the maximum
settable temperature), then the compressor will not start, but only start electric heating; if
the water tank temperature ≤55
℃
, both the compressor and electric heater will start.
◎
When the water tank temperature ≥70
℃
and the protection temperature lasts for
30minutes ≥65
℃
, exit the high temperature Antisepsis;
◎
After entering high temperature Antisepsis, if the temperature of the hot water tank does
not reach 65°C after 1 hour, the high temperature Antisepsis program will be forced to exit;
Target Temperature Auto Adjustment Logic ( Under Heating Mode)
◎
The target temperature under heating mode can be automatically adjusted according to
the ambient temperature.
◎
Entry conditions
When Parameter enables automatic adjustment mode of heating target temperature.
Содержание V1 Series
Страница 9: ...8 V1 18 V1 23 V1 28 V1 35...
Страница 10: ...9 Exploded view V1 08...
Страница 11: ...10 V1 13...
Страница 12: ...11 V1 18 23...
Страница 13: ...12 V1 28 35...
Страница 16: ...15 Figure 2 Figure 3...
Страница 18: ...17 Figure 7 Figure 8...
Страница 20: ...19 Figure 11 Figure 12 Figure 13...
Страница 23: ...22 Electrical Wiring Diagram 1 Single phase system V1 08...
Страница 24: ...23 2 Three phase system V1 13 18 23...
Страница 25: ...24 3 Three phase system V1 28 35...