Chapter 10 __________________________________________________________ Troubleshooting
VAISALA______________________________________________________________________ 171
See also
Chapter 10 Troubleshooting, on page 167
.
Rain and Wind Sensor Heating
Control
The supervisor message
aSU
shows you continuously monitored
information about rain and wind sensor heating (heating temperature Th
and heating voltage Vh). See
Supervisor Message on page 144
.
Table 28
Error Messaging/Text Messages
Text message
identifier (in
NMEA 0183 v3.0
protocol only)
Text Message
Interpretation and action
01
Unable to measure error The requested parameters are not activated in the
message and check the parameter section fields. See
Chapter 8 Sensor and Data Message Settings, on page
127
.
02
Sync/address error
The device address in the beginning of the command is
invalid. Ask the device address with the
?!
(SDI-12) or
?<cr><lf>
(ASCII and NMEA) command and retype the
command with the correct address.
03
Unknown cmd error
The command is not supported, use the correct
command format. See
04
Profile reset
Checksum error in configuration settings during power-
up. Factory settings used instead.
05
Factory reset
Checksum error in calibration settings during power-up.
Factory settings used instead.
06
Version reset
New software version in use.
07
Start-up
Software reset. Program starts from the beginning.
08
Use chksum xxx
Given checksum not correct for the command. Use the
proposed checksum.
09
Measurement reset
The ongoing measurement of all the sensors interrupted
and started from the beginning.
10
Rain reset
The precipitation sensor counter reset.
11
Inty reset
Precipitation sensor intensity counter reset.
NOTE
When a WXT530 Series transmitter is used on an RS-485 bus with
other polled devices, the error messaging feature must be disabled
using the command:
0SU,S=N<crlf>
.