The Safety Barrier Wiring Set consists of wiring for 4 devices. Any unused wires in the
Wiring Set have been placed in the cable duct at the factory. If you have, for example,
3 barriers installed on a DIN rail, and want to complete the set by installing a fourth one, use
the existing barrier wires present in the cable duct.
1. De-energize the cabinet:
a. Switch off mains power.
b. Switch off the circuit breaker located inside the cabinet.
1
Circuit breaker
c. Disconnect the safety barrier power wire connector from the power block located on
the right-hand side of the cabinet.
2. Remove the cable duct cover above the safety barriers.
3. Mount the DL4000 data logger (or loggers), as shown in the following steps.
Each set of 4 safety barriers requires a data logger of its own. If you are installing the
second, third, or fourth barrier to complete a set of 4, the steps to mount a new data
logger are not relevant, as you can connect the new barrier(s) to the existing data
logger.
CAB100 Installation Guide
M212242EN-B
72