Installation instructions geoTHERM VWS/VWW 0020051574_01
82
Description
Unit
VWW 220/2
VWW 300/2
VWW 380/2
VWW 460/2
Hydraulic connections
- Heating circuit flow and return
- Heat source flow and return
mm
mm
G 1 1/2"
G 1 1/2"
Heat source circuit
- Max. operating pressure
- Min. inlet temperature
- Max. inlet temperature
MPa (bar)
°C
°C
- Nominal flow rate dT 3K
- Residual head dT 3K
- Nominal flow rate dT 4K
- Residual head dT 4K
- Electrical power consumption - pump
l/h
mbar
l/h
mbar
W
6417
4813
8760
6570
10800
8100
13080
9810
CH circuit
- Max. operating pressure
- Min. flow temperature
- Max. flow temperature
MPa (bar)
°C
°C
0.3 (3)
25
62
- Nominal flow rate dT 5K
- Residual head dT 5K
- Nominal flow rate dT 10K
- Residual head dT 10K
- Electrical power consumption - pump
l/h
mbar
l/h
mbar
W
5099
106
2603
31
6960
152
3600
45
8700
198
4500
58
10440
251
5520
76
Coolant circuit
- Coolant type
-
R 407 C
- Quantity
kg
4.3
5,99
6,7
8,6
- Permissible operating overpressure
- Compressor type
- Oil
- Oil filling capacity
MPa (bar)
-
-
l
2.9 (29)
Scroll
Ester
4
4
4,14
4,14
Heat pump performance data
W10W35 dT5
- Heating output
- Power consumption
- Performance figure/COP
W10W35 dT10
- Heating output
- Power consumption
- Performance figure/COP
W10W55
- Heating output
- Power consumption
- Performance figure/COP
kW
kW
-
kW
kW
-
kW
kW
-
29,9
5.8
5.2
30,2
5.5
5.5
26,9
7,6
3.5
41,6
7,8
5.3
42,4
7.5
5.7
37,2
10.4
3,6
52,6
9.8
5.3
52,3
9.4
5.5
47,4
12,9
3,6
63,6
12,4
5.1
64,7
12,0
5,4
57,3
15,8
3,6
Internal sound level
dBA
63
63
63
65
Conforms to safety regulations
-
CE-1027 mark
Low Voltage Directive 73/23/EWG
EMC Directive 89/336/EWG
EN 60335
ISO 5149
Pressure equipment directive 97/23/EC, category II
Table 13.2 Technical data - VWW (cont)
13 Technical data