Installation instructions geoTHERM VWS/VWW 0020051574_01
72
9.4
Test operation and restarting
d
Danger!
Risk of injury!
The heat pump may only be put into op-
eration again after all the cladding sec-
tions have been fitted.
• Fit all the heat pump cladding sections as described in
Chap. 6.10.
• Start up the heat pump.
• Check the heat pump for correct functioning.
10 Troubleshooting
and
diagnosis
d
Danger!
Troubleshooting and diagnostics meas-
ures may only be carried out by a recog-
nised expert technician company.
e
Danger!
Risk of fatal electric shock from touch-
ing live connections! Before commencing
work on the heat pump, disconnect the
power supply (circuit breaker) and se-
cure it against being switched on again
inadvertently.
10.1
Error messages on the controller
Error messages appear on the display approximately
20 seconds after the error has occurred and are written
to the controller's error memory if the error is present
for approximately 3 minutes. You can call up the error
memory in Menu I1. As long as the fault is present, you
can call up the fault display by turning the dial 1 x to
the left, starting from the graphics display.
Error History
I1
Fault number
> 1
Fault code
41
16.02.08 07:18
Error CH circuit
Sensor T3 heat source
Fig. 10.1 Error message in error memory, Menu I1
The geoTHERM control system recognises three differ-
ent types of malfunction:
- Malfunction of
components
that are connected via
the
eBUS
.
-
Temporary shut-down
The heat pump remains in operation. The error is dis-
played and disappears independently when the cause
of the fault is removed.
-
Fault-induced shutdown
The heat pump is shut down. It can only be restarted
by resetting the error after removing the cause of the
fault (see Menu I 1).
- In addition,
other errors/malfunctions
can occur on
the unit or system.
9 Inspection and maintenance
10 Troubleshooting and diagnosis