Installation instructions geoTHERM VWS/VWW 0020051574_01
7.3
Carrying out the initial commissioning
As soon as the heat pump is supplied with power during
the initial commissioning, an internal self-test starts au-
tomatically, whereby the heat pump checks itself and
any connected components for functional capability. At
the same, the sensor configuration is checked, the
phase sequence of the AC supply is determined and the
functioning of the sensors in use is checked.
If the self-test was not successful, an error message ap-
pears on the controller display (see Chap. 10, "Trouble-
shooting and diagnosis").
• Switch on the circuit breaker, so that the heat pump is
supplied with power.
The heat pump starts, the controller software is initial-
ised:
Vaillant
Loading...
Fig. 7.2 Controller being initialised
After a short time the controller is ready for operation
and detects that this is an initial commissioning. During
the initial installation the controller always starts with
the Installation Assistant - Menu A1.
Installation
A1
Language selection
Language
> GB english
> Select
Fig. 7.3 Menu A1: Language selection
Change the language setting if necessary and turn the
dial to the next menu.
Installation assistant
A2
Hydraulic scheme
0
Electrical plan
0
Accept change
No
> Select
Fig. 7.4 Menu A2: Installation assistant
h
The heat pump type has already been
set at the factory and may not be
changed!
Selecting the hydraulic plan
a
Caution!
Possible malfunctions.
Take care to select the correct hydraulic
plan, as otherwise malfunctions can
occur in the system.
• Turn the dial until the cursor
>
is pointing to the hy-
draulic plan no.
• Press the dial. The parameter will be activated and
displayed in inverse video.
• Turn the dial until the hydraulic plan matching your
system has been selected (see Table 7.1).
The hydraulic diagrams for your system are shown in
Chapters 6.6.2 to 6.6.7.
• Press the dial to confirm the selection.
Hydraulic plan No.
Buffer tank
CH circuit
DHW cylinder
External passive
cooling
Probe
VR 60 connection
Fig. No.
1
X
AF, VF2
prohibited
6.8
2
X
X
AF, VF1, VF2,
RF1
possible
6.9
3
X
X
AF, SP, VF2
prohibited
6.10
4
X
X
X
AF, SP, VF1,
VF2, RF1
possible
6.11
9*
X
X
X
AF, VF1, VF2,
RF1
required
*
10
X
X
X
X
AF, SP, VF1,
VF2, RF1
required
6.12
Table 7.1 Selecting the Hydraulic plan No.
* same as hydraulic plan 10, but without domestic hot water cyl-
inder
Start-up 7