Installation 5
0020200969_04 Installation manual
37
5.7.4
Installing the air clamps
1.
Connect all of the disconnection points with air clamps.
min. 30 mm
70 mm
1
2
3
48 mm
min. 15 mm
1
2
3
30 mm
min. 12 mm
1
2
3
40 mm
min. 15 mm
1
2
3
2.
Slide the air clamps centrally over the disconnection
point of the air pipes and tighten the screws
(1)
.
–
Air pipes distance:
≤
5 mm
Danger!
Risk of poisoning due to escaping flue
gas.
Flue gas can escape if the flue pipe is dam-
aged.
▶
Take care that the flue pipe is not dam-
aged when drilling.
3.
Drill holes into the air pipe through the holes in the air
clamp
(3)
.
Danger!
Risk of poisoning due to escaping flue
gas.
Flue gases may escape as a result of pipes
that are not securely connected to each
other.
▶
Secure the clamps and air pipes using the
supplied bolts.
4.
Insert the safety screws
(2)
.
5.7.5
Securing the telescopic extension
Ø 3 mm
1
2
Danger!
Risk of poisoning due to escaping flue
gas.
Flue gas can escape if the flue pipe is dam-
aged.
▶
Take care that the flue pipe is not dam-
aged when drilling.
1.
Drill a hole
(1)
into the overlapping air pipes.