X
5
EIP
01
Ethernet IP with
115
VAC / Encoder Interface Option Board
vacon
19
Table 11: Control Supervisor Object
(Class Code 0x29, Control Supervisor Class (41) - Instance Attributes (1)
#
Attribute Name
Services
Default,
Minimum,
Maximum
Data
Type
Description
3
0x03
Run1
Get_Attribute_Single
Set_Attribute_Single
0
0
1
4
Run Forward Request
4
0x04
Run2
Get_Attribute_Single
Set_Attribute_Single
0
0
1
4
Run Reverse Request
5
0x05
NetCtrl
Get_Attribute_Single
Set_Attribute_Single
0
0
1
4
Requests Run/Stop control to be
local or from network
6
0x06
State
Get_Attribute_Single
N/A
0
7
8
State of Control Supervisor Instance:
1 = Startup
2 = Not_Ready
3 = Ready
4 = Enabled
5 = Stopping
6 = Fault_Stop
7 = Faulted
7
0x07
Running1
Get_Attribute_Single
N/A
0
1
4
Running Forward Status:
0 = Other state
1 = Running Forward
8
0x08
Running2
Get_Attribute_Single
N/A
0
1
4
Running Reverse Status:
0 = Other state
1 = Running Reverse
9
0x09
Ready
Get_Attribute_Single
N/A
0
1
4
Ready to Accept a Run Event:
0 = Other state
1 = Ready to accept a Run event
10
0x0A
Faulted
Get_Attribute_Single
N/A
0
1
4
Fault Occurred:
0 = No faults present
1 = Fault occurred (latched)
12
0x0C
FaultRst
Get_Attribute_Single
Set_Attribute_Single
0
0
1
4
Fault Reset Request:
0 = No action
0 -> 1 = Fault reset request
1 = No action
13
0x0D
FaultCode
Get_Attribute_Single
N/A
0
65535
2
If in faulted state, FaultCode
indicates the fault that caused the
transition to be in a faulted state. The
fault codes are listed in the Ethernet/
IP specifications
15
0x0F
CtrlFromNet
Get_Attribute_Single
N/A
0
1
4
Status of Run / Stop control source:
0 = Control is local
1 = Control is from the network
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]