34 • vacon
service data (sdo)
Tel.+358-(0)201-21
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
8
0A
Standard Error Field
0x00000000
0x00000000
0xFFFFFFFF
u32 ro
1005
00
cob-id sync message
0x80000080
0x00000001
0xFFFFFFFF
u32 ro cob-id used for syncronize PDO messages
100C
00
Guard Time
0x03E8
0x0000
0xFFFF
u16 rw
This entry contains the guard time in
milliseconds. It is 0, if not used.
Unit: ms
100D
00
Life Time Factor
0x02
0x00
0xFF
u8 rw
The life time factor multiplied with the guard time gives
the life time for the device. It is 0, if not used.
1018
Identity Object
This object contains general information about the
device.
00
Number of entries
0x4
0x1
0x4
u8 ro
01
Vendor Id
0x00000090
0x0
0xFFFFFFFF
u32 ro
Sub-Index 1 contains a unique value allocated each
manufacturer.
02
Product Code
0x00000119
0x0
0xFFFFFFFF
u32 ro
Sub-Index 2 identifies the manufacturer specific product
code (device version).
03
Revision number
0x00000001
0x0
0xFFFFFFFF
u32 ro
Sub-Index 3 contains the revision number. Bit 31-16 is
the major revision number and Bit 15-0 the minor
revision number.
04
Serial number
0x0
0x0
0xFFFFFFFF
u32 ro
Sub-Index 4 identified a manufacturer specific serial
number.
Server SDO Parameters
1200
Server SDO Parameter
The object contains the parameters for the SDOs for
which the device is the server.
00
Number of Entries
0x02 0x02
0x02
u8 ro
01
COB-ID Client -> Server
0x600+NodeID
0x00000601
0xFFFFFFFF
u32 ro
02
COB-ID Server -> Client
0x580+NodeID
0x00000581
0xFFFFFFFF
u32 ro
Receive PDO Communication Parameters
1400
Receive PDO 1
Communication
Parameter
It contains the communication parameters of the first
PDO the device is able to receive.
00
Number of Entries
0x02 0x02
0x05
U8 ro
Sub-index 0 contains the number of PDO-parameters
implemented.
01
COB-ID
0x200+NodeID
0x00000201
0xFFFFFFFF
U32 ro
Sub index 1 describes the COB-ID. If bit 31 is set the PDO
is disabled.
02
Transmission Type
0xFF
0x00
0xFF
u8 ro
The transmission mode is defined by sub-index 2.
Value 0xFF (255) = asyncronous transmission mode (
=event driven )
1405
Receive PDO 6
Communication
Parameter
It contains the communication parameters of the second
PDO the device is able to receive.
00
Number of Entries
0x02 0x02
0x05
u8 ro
Sub-index 0 contains the number of PDO-parameters
implemented.
01
COB-ID
0x300+NodeID
0x00000301
0xFFFFFFFF
u32 ro
Sub index 1 describes the COB-ID. If bit 31 is set the PDO
is disabled.
02
Transmission Type
0xFF
0x00
0xFF
u8 ro
The transmission mode is defined by sub-index 2.
Value 0xFF (255) = asyncronous transmission mode (
=event driven )