36 • vacon
service data (sdo)
Tel.+358-(0)201-21
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
8
objects. All further entries define the data by it's index,
sub-index and length.
00
Number of Entries
0x04
0x00
0x40
u8 ro
01
PDO Mapping Entry
0x27D60010
0x00000000
0xFFFFFFFF
u32 ro
02
PDO Mapping Entry
0x27D70010
0x00000000
0xFFFFFFFF
u32 ro
03
PDO Mapping Entry
0x27D80010
0x00000000
0xFFFFFFFF
u32 ro
04
PDO Mapping Entry
0x27D90010
0x00000000
0xFFFFFFFF
u32 ro
Transmit PDO Communication Parameters
1800
Transmit PDO 1
Communication
Parameter
It contains the communication parameters of the first
PDO the device is able to transmit.
00
Number of Entries
0x04
0x02
0x05
u8 ro
Sub-index 0 contains the number of PDO-parameters
implemented.
01
COB-ID
0x180+NodeID
0x00000181
0xFFFFFFFF
u32 ro
Sub index 1 describes the COB-ID. If bit 31 is set the PDO
is disabled.
02
Transmission Type
0xFF
0x00
0xFF
u8 ro
The transmission mode is defined by sub-index 2.
Value 0xFF (255) = asyncronous transmission mode (
=event driven )
03
Inhibit Time
0x03E8
0x0000
0xFFFF
u16 rw
An inhibit time can be defined on sub-index 3 in 100 µs.
This time is minimum interval for PD transmission.
Default 100 ms
04
Compatibility Entry
0x03
0x00
0xFF
u8 ro
1805
Transmit PDO 6
Communication
Parameter
It contains the communication parameters of the PDO 6
the device is able to transmit.
00
Number of Entries
0x05
0x02
0x05
u8 ro
Sub-index 0 contains the number of PDO-parameters
implemented.
01
COB-ID
0x280+NodeID
0x00000281
0xFFFFFFFF
u32 ro
Sub index 1 describes the COB-ID. If bit 31 is set the PDO
is disabled.
02
Transmission Type
0xFF
0x00
0xFF
u8 rw
The transmission mode is defined by sub-index 2.
Value 0xFF (255) = asyncronous transmission mode (
=event driven )
03
Inhibit Time
0x03E8
0x0000
0xFFFF
u16 rw
An inhibit time can be defined on sub-index 3 in 100 µs.
This time is minimum interval for PD transmission.
Default 100 ms
04
Compatibility Entry
0x03
0x00
0xFF
u8 ro
05
Event Timer
0x0000
0x0000
0xFFFF
u16 rw
Event Time can be define on subindex 5 in 1ms
resolution. This is the time interval PDO will be
transmitted.
Value 0 = Disable Event Timer
1814
Transmit PDO 21
Communication
Parameter
It contains the communication parameters of the PDO
21 the device is able to transmit.
00
Number of Entries
0x05
0x02
0x05
u8 ro
Sub-index 0 contains the number of PDO-parameters
implemented.
01
COB-ID
0x380+NodeID
0x00000381
0xFFFFFFFF
u32 ro
Sub index 1 describes the COB-ID. If bit 31 is set the PDO
is disabled.
02
Transmission Type
0xFF
0x00
u8 rw
The transmission mode is defined by sub-index 2.
Value 0xFF (255) = asyncronous transmission mode (