appendix c – process data contents
Process Data OUT (Slave
Master)
The fieldbus master can read the frequency converter’s actual values using process data variables.
Basic, Standard, Local/Remote, Multi-Step, PID control and Pump and fan control
applications use
process data as follows:
Data
Value
Unit
Scale
Process data OUT 1
Output Frequency
Hz
0,01 Hz
Process data OUT 2
Motor Speed
rpm
1 rpm
Process data OUT 3
Motor Current
A
0,1 A
Process data OUT 4
Motor Torque
%
0,1 %
Process data OUT 5
Motor Power
%
0,1 %
Process data OUT 6
Motor Voltage
V
0,1 V
The
Multipurpose
application has a selector parameter for every Process Data. The monitoring values
and drive parameters can be selected using the ID number (see NX All in One Application Manual,
Tables for monitoring values and parameters). Default selections are as in the table above.
Process Data IN (Master -> Slave)
ControlWord, Reference and Process Data are used with All-in One applications as follows:
Basic, Standard, Local/Remote, Multi-Step applications
Data
Value
Unit
Scale
Reference
Speed Reference
%
0.01%
ControlWord
Start/Stop
Command
Fault reset
Command
-
-
PD1 – PD6
Not used
-
-