vacon • 34
Commissioning
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
Example 3: OPTBJ board with SS1 and safety reset or EN 60204-1 stop category 1.
The figure above presents a connection example of OPTBJ board for SS1 safety function with ex-
ternal safety relay module and with safety reset.
The external safety relay module is connected to the switch S1. The used power supply to switch S1
is 230 VAC as an example. The safety relay module is connected to OPTBJ board with 4 wires as
shown in Figure above.
To configure the drive to perform the fast deceleration with a ramp, it is recommended to use Quick
Stop -function that is activated by digital input, for example DI6 as in Example 3 above. See the ap-
plication manual for correct parametrization of Quick Stop -function.
When the switch S1 is activated (contacts open), the drive starts ramping down the output frequency
until the delay of the safety relay has passed. After safety relay time delay, the drive goes to STO
state. If the motor is still running, it stops by coasting. If STO fault action is parameterized as
"Alarm", the drive indicates: "30 Safe torque off". Regardless of the parameterization, activation of
STO function causes a coasting stop for motor.
To allow the returning of the drive to ready state after S1 is deactivated (contacts closed) and safety
relay is resetted, STO Fault action needs to be parameterized as "Alarm". If STO Fault action is pa-
rameterized as "Fault", also the drive needs to be reset to allow ready state. See application manual
for related parameters.
To start the motor operation again, following sequence is performed.
•
Release the switch S1 (contacts closed). The hardware is now enabled and the drive returns to ready
state. An alarm indication for STO actiavation is displayed if STO Fault action is parameterized as
"Alarm".
•
Acknowledge the releasing of switch by resetting the safety relay. The drive returns to the ready state.
•
Giving a valid start command starts running the motor
F1
1
2
3
4
5
6
L1
L2
MAIN CIRCUIT
L3
PE
PE
L1
L2
L3
U
V
W
PE
2
7
PE
PE
PE
W1
M1
M
3
~
U1
1
V1
W1
2
PE
R1
SPEED REFERENCE
S
CCW
CW
W12
1sh
1r
2sh
2p
2s
Basic I/O
1
+10Vref
1
2
AI1+
2
3
AI1
3
OPTBJ
SLOT E
1
STO1+
2
STO1
S6
START
13
14
4
AI2+
4
5
AI2
5
6
24Vout
6
7
GND
7
3
STO2+
4
STO2
S7
STOP
11
12
8
DI1
8
9
DI2
9
10
DI3
10
11
CM
11
25
RO1 C
26
RO1 NO
28
TI1+
12
24Vout
12
13
GND
13
14
DI4
14
15
DI5
15
X23
29
TI1
16
DI6
16
17
CM
17
18
AO1+
18
19
AO/GND
19
30
+24Vin
20
PE
OFF
A
RS485
B
RS485
21
22
X10
Installed
PE
Short circuit and earth
fault protected supply
0V
PE
PE
A10
W3
1r
2r
57
58
+24V
67
68
PE
13
14
23
24
33
34
41
42
24VDC
A1
A2
0VDC
+
S10
S1
11
12
S11 S12 S21
21
22
PHOENIX CONTACT
S22
S33
PSRSCP24DC/ESD/5X1/1X2/300
RESET
S34
S35
Bridge between S33/S35 for automatic reset.
(Not allowed with emergency stop)
RS1
RS2
RS1
RS2
RAMP STOP
3046A_UK
AO1
RS485
U
U
U
ON
OFF
I
I
I
AI2
AI1
ON
OFF
DGND
Содержание optbj
Страница 2: ......
Страница 5: ...Approvals vacon 5 Local contacts https www danfoss com en contact us contacts list 1 ...
Страница 6: ...1 vacon 6 Approvals Local contacts https www danfoss com en contact us contacts list ...
Страница 7: ...Approvals vacon 7 Local contacts https www danfoss com en contact us contacts list 1 ...
Страница 8: ...1 vacon 8 Approvals Local contacts https www danfoss com en contact us contacts list ...
Страница 9: ...Approvals vacon 9 Local contacts https www danfoss com en contact us contacts list 1 ...