6
vacon • 32
Commissioning
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
6.2
Wiring examples
The examples in this chapter show the basic principles for wiring OPTBJ board. Local standards
and regulations should be always followed in the final design.
Example 1: OPTBJ board without reset for Safe Torque Off (STO)
The figure above shows a connection example of OPTBJ board for Safe Torque Off safety function
without reset. The switch S1 is connected with 4 wires to the OPTBJ board as shown above.
When the switch S1 is activated (contacts open), the drive goes to STO state and motor (if running)
will stop by coasting. If STO fault action is parameterized as "Alarm", the drive indicates: "30 Safe
torque off". Regardless of the parameterization, activation of STO function causes a coasting stop
for motor.
To allow the returning of the drive to ready state without a reset after S1 is deactivated (contacts
closed), STO Fault action must be parameterized as "Alarm". See application manual for related pa-
rameters.
To start the motor operation again, the following sequence is performed.
•
Release the switch S1 (contacts closed). The hardware is now enabled and the drive returns to ready
state.
•
Giving a valid start command starts running the motor.
NOTE!
According to EN 60204-1 (Safety of machinery - Electrical equipment of machines), the re-
setting of the emergency stop request (e.g. releasing of emergency stop button) must not restart
the drive.
NOTE!
The VACON
®
100 default application software uses edge-sensitive start as a default start
command. With the edge-sensitive start command, disactivating the STO does not cause immediate
start.
F1
1
2
3
4
5
6
L1
L2
MAIN CIRCUIT
L3
PE
PE
L1
L2
L3
U
V
W
PE
2
7
PE
PE
PE
W1
M1
M
3
~
U1
1
V1
W1
2
PE
R1
SPEED REFERENCE
S
CCW
CW
W12
1sh
1r
2sh
2p
2s
Basic I/O
1
+10Vref
1
2
AI1+
2
3
AI1
3
OPTBJ
SLOT E
1
STO1+
2
STO1
S1
11
12
W10
1r
2r
1b
2b
S6
START
13
14
4
AI2+
4
5
AI2
5
6
24Vout
6
7
GND
7
3
STO2+
4
STO2
21
22
S7
STOP
11
12
8
DI1
8
9
DI2
9
10
DI3
10
11
CM
11
25
RO1 C
26
RO1 NO
28
TI1+
12
24Vout
12
13
GND
13
14
DI4
14
15
DI5
15
X23
OFF
29
TI1
16
DI6
16
17
CM
17
18
AO1+
18
19
AO/GND
19
30
+24Vin
20
PE
Safe torque off
+24V
0V
A
RS485
B
RS485
21
22
AO1
RS485
U
U
U
ON
OFF
I
I
I
AI2
AI1
Short circuit and earth
fault protected supply
ON
OFF
DGND
X10
Installed
3044B_UK.eps
Содержание optbj
Страница 2: ......
Страница 5: ...Approvals vacon 5 Local contacts https www danfoss com en contact us contacts list 1 ...
Страница 6: ...1 vacon 6 Approvals Local contacts https www danfoss com en contact us contacts list ...
Страница 7: ...Approvals vacon 7 Local contacts https www danfoss com en contact us contacts list 1 ...
Страница 8: ...1 vacon 8 Approvals Local contacts https www danfoss com en contact us contacts list ...
Страница 9: ...Approvals vacon 9 Local contacts https www danfoss com en contact us contacts list 1 ...