Commissioning
vacon • 33
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
6
Example 2: OPTBJ board with reset for Safe Torque Off or EN 60204-1 stop category 0.
The figure above presents a connection example of OPTBJ board for STO safety function with reset.
The switch S1 is connected with 4 wires to the OPTBJ board as shown above. The digital input 3
(DIN3), for example, is wired for the fault reset function. The reset function (not part of any safety
function) can be programmed to any of the available digital inputs.
To prevent starting the motor without reset, STO fault action has to be parameterized as "Fault".
See application manual for related parameters.
When the switch S1 is activated (contacts open), the drive goes to STO state and motor (if running)
stops by coasting. The drive indicates: "30 SafeTorqueOff".
To start the motor operation again, the following sequence is performed.
•
Release the switch S1 (contacts closed). The hardware is now enabled but the drive continues to dis-
play the fault "30 SafeTorqueOff".
•
Acknowledge the releasing of switch by edge sensitive reset function. The drive returns to the ready
state.
•
Giving a valid start command starts running the motor.
NOTE!
According to EN 60204-1 (Safety of machinery - Electrical equipment of machines), the re-
setting of the emergency stop request (e.g. releasing of emergency stop button) must not restart
the drive.
NOTE!
The VACON
®
100 default application software uses edge-sensitive start as a default start
command. With the edge-sensitive start command, disactivating the STO does not cause immediate
start.
NOTE!
For EN 60204-1 emergency stop according to stop category 0, use the emergency stop but-
ton.
F1
1
2
3
4
5
6
L1
L2
MAIN CIRCUIT
L3
PE
PE
L1
L2
L3
U
V
W
PE
2
7
PE
PE
PE
W1
M1
M
3
~
U1
1
V1
W1
2
PE
R1
SPEED REFERENCE
S
CCW
CW
W12
1sh
1r
2sh
2p
2s
Basic I/O
1
+10Vref
1
2
AI1+
2
3
AI1
3
OPTBJ
SLOT E
1
STO1+
2
STO1
S1
11
12
W10
1r
2r
1b
2b
S6
START
13
14
4
AI2+
4
5
AI2
5
6
24Vout
6
7
GND
7
3
STO2+
4
STO2
21
22
S7
STOP
11
12
S8
RESET
13
14
8
DI1
8
9
DI2
9
10
DI3
10
11
CM
11
25
RO1 C
26
RO1 NO
28
TI1+
12
24Vout
12
13
GND
13
14
DI4
14
15
DI5
15
X23
OFF
29
TI1
16
DI6
16
17
CM
17
18
AO1+
18
19
AO/GND
19
30
+24Vin
20
PE
+24V
0V
Safe torque off
A
RS485
B
RS485
21
22
Short circuit and earth
fault protected supply
X10
Installed
3045B_UK
AO1
RS485
U
U
U
ON
OFF
I
I
I
AI2
AI1
ON
OFF
DGND
Содержание optbj
Страница 2: ......
Страница 5: ...Approvals vacon 5 Local contacts https www danfoss com en contact us contacts list 1 ...
Страница 6: ...1 vacon 6 Approvals Local contacts https www danfoss com en contact us contacts list ...
Страница 7: ...Approvals vacon 7 Local contacts https www danfoss com en contact us contacts list 1 ...
Страница 8: ...1 vacon 8 Approvals Local contacts https www danfoss com en contact us contacts list ...
Страница 9: ...Approvals vacon 9 Local contacts https www danfoss com en contact us contacts list 1 ...