Commissioning
vacon • 31
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
6
Figure 14. Structure of cable with two individually shielded twisted pairs
X = Not recommended due to causes of electromagnetic disturbances, safety actuator configuration or behavior
in failure situations.
Table 9. Recommended maximum cable lengths
Safety actuator type
Diagnostics on safety
actuator
Cable type
Used STO input connection
STO
connection
example 1
STO
connection
example 2
STO
connection
example 3
Undiagnosed safety actuator
(i.e. emergency stop button or
relay contact)
No diagnostics
Shielded
X
200 m
200 m
Unshielded
X
30 m
X
Safety actuator with diagnosed
outputs (i.e. safety PLC)
Outputs diagnosed using
e.g. dark test pulse,
light test pulse not used
Shielded
200 m
200 m
200 m
Unshielded
30 m
30 m
X
Outputs diagnosed using
light test pulse
Shielded
200 m
X
X
Unshielded
30 m
X
X
Individual pair
Overall shield
(Optional)
Pair shield
Cable jacket
11860_uk
Содержание optbj
Страница 2: ......
Страница 5: ...Approvals vacon 5 Local contacts https www danfoss com en contact us contacts list 1 ...
Страница 6: ...1 vacon 6 Approvals Local contacts https www danfoss com en contact us contacts list ...
Страница 7: ...Approvals vacon 7 Local contacts https www danfoss com en contact us contacts list 1 ...
Страница 8: ...1 vacon 8 Approvals Local contacts https www danfoss com en contact us contacts list ...
Страница 9: ...Approvals vacon 9 Local contacts https www danfoss com en contact us contacts list 1 ...