12 • vacon
INSTALLATION
Tel: +358-201-2121 • Fax: +358-201-212 205
4.1
Free space around the cabinet
Enough space must be left above, behind and in front of the cabinet to ensure sufficient cooling and
space for maintenance.
The amount of cooling air required is indicated in the table below. Also make sure that the tempera-
ture of the cooling air does not exceed the maximum ambient temperature of the inverter.
200 mm
800 mm
25 mm
Figure 4-3. Space to be left free above (left) and in front of (right) the cabinet.
Type
Cooling air required [m
3
/h)
NXV0010
300
NXV0015
300
NXV0020
425
NXV0025
425
NXV0030
425
NXV0040
700
NXV0050
700
NXV0080
800
NXV0100
800
Table 4-1. Required cooling air