Step 10. Installing the Keypad Interface Module (KIM) into the AC Drive (XRKMK only)
1. Position the keypad interface module (KIM) into the door opening.
2. Fasten the keypad module with the four (4) M5 x 12 screws provided, limiting torque to 26 in-lb maximum.
3. Reconnect the ribbon cable to the connector socket and ensure it is still retained by the cable clamp on the
door.
4. Secure the multi-conductor cable using the loop clamp on the lower portion of the keypad interface board.
You may need to loosen the cable clamp to install the cable in it.
5. Terminate the individual wires to TB1 and TB2 as in
Step 6, #6
. Note the wire color assignments; this will be
useful in
Step 12
. For your convenience, TB1 and TB2 terminal blocks are removable.
6. Secure the cable shield(s) to Terminal 1.
7. Route the cabling as needed to avoid any damage. The multi-conductor must be routed through an unused
conduit entry. Be sure to use appropriate conduit fittings for your environment. Additional wire ties and tie
bases are provided to allow strain relief for the wire.
8. As you fasten the enclosure, limit the installation torque to 26 in-lb. maximum.
Figure 10: Installing the KIM into the AC Drive (XRKMK Option)