32 COI/TZIDC/TZIDC-200-EN |
TZIDC, TZIDC-200
3.15.3
IP-TYP – Type of the I/P module
Use this parameter to adapt the positioner software to the
installed I/P module. This is requ ired when installing a di
ff
erent
I/P module type.
CAUTION
Risk of injury!
For safety reasons, after loading the factory settings you
must check whether the I/P module type that is set matches
the actual I/P module type pres ent in the device. Otherwise
dangerous situations may occu r when operating in control
mode. It may happen that the act uator is driven at full speed
to the end position.
CAUTION
For safety reasons, after rest oring the positioner to the
factory settings you must check whether this parameter has
been correctly set.
3.15.4
IP_COMP – IP Compensation
This function is reserved for use by ABB Service only.
3.15.5
HART_REV – HART version
As of
fi
rmware version 5, the positioner o
ff
ers communication
via both standard HART 5 and HART 7. To select, use the
arrow keys
©
or
ª
.
Squawk command:
A standardized HART-7 comma nd causes the bottom menu
line in the HMI of the addressed device to
fl
ash. This visual aid
makes it easier to identify the addressed device in the system.
3.15.6
EXIT – Return to operating level
With this parameter you can leave the con
fi
guration level. The
positioner returns to the operating level. Here you can either
save data in the non-volatile me mory or discard all previously
made changes (also the changes in other parameter groups).
To leave the con
fi
guration level (with or without saving), press
and hold
ENTER
until the countdown from 3 to 0 is
fi
nished.
The active saving process is indicated by the message
NV_SAVE
. After saving a plausibility check is executed.
If an error occurs during the check or while saving, the data
cannot be saved and an error message is displayed instead
(see Chapter "Error codes" on page 33).
Selection
NV_SAVE
Saves settings in the non-volatile memory.
CANCEL
Discards all changes made since the last
permanent save operation.
Change from two to one column