TZIDC, TZIDC-200
| COI/TZIDC/TZIDC-200-EN 37
4.4
Error handling
4.4.1
Positioner vibrates
The positioner vibrates (oscillates) in control modes
1.0
and
1.1
.
Press the
©
button. Is the current value stable?
No
Check power source or PLS.
Yes
Switch the positioner to operating mode
1.2
(manual) and set it
to a position of approx. 50 % us ing the local push buttons. Is
the position stable?
No
Check the piping and actuator for leak age. If leakage is detected, send the
positioner for repair.
Yes
Start Autostroke and save the va lues. Switch the positioner to
operating mode
1.1
.
Is the position stable?
Yes
Good job! The work activities are completed.
No
Switch the positioner to operating mode
1.0
(adaptive) for
4 to 5 hours in order to optimize the control response. Several
changes to the setpoint signal are required.
Is the positioner function stable?
Yes
Good job! The work activities are completed.
No
Increase the dead band
(DEADBAND)
.
Is the valve function stable?
Yes
Good job! The work activities are completed.
No
The friction of the valve is too grea t or Slipstic e
ff
ect. Check the
valve.