background image

 

18  COI/TZIDC/TZIDC-200-EN   | 

TZIDC, TZIDC-200 

 

 

3.7.3

 

ZERO_POS – Zero position 

 

 

 
With this parameter you can assign the zero position of the 
display to the zero position of the valves and 

fi

ttings. It also 

allows you to select the direction of rotation of the sensor 
shaft (looking at the open housing). 
 

NOTE

 

 

Normally, the zero position is determined automatically and 
saved during standard Autoadjust. 

 

Linear actuators 

Î

 “counterclockwise

 

Rotary actuators 

Î

 “clockwise” 

 

Selection 

CLOCKW 

Limit stop reached turning clockwise 

CTCLOCKW 

Limit stop reached turning counterclockwise 

 

3.7.4

 

EXIT – Return to operating level 

 

 

 
With this parameter you can leave the con

fi

guration level. The 

positioner returns to the operating level. Here you can either 
save data in the non-volatile me mory or discard all previously 
made changes (also the changes in other parameter groups). 
 
To leave the con

fi

guration level (with or without saving), press 

and hold 

ENTER

 until the countdown from 3 to 0 is 

fi

nished.  

 
The active saving process is indicated by the message 

NV_SAVE

. After saving a plausibility check is executed. 

 
If an error occurs during the  check or while saving, the data 
cannot be saved and an error  message is displayed instead 
(see Chapter "Error codes" on page 33). 
 

Selection 

NV_SAVE 

Saves settings in the non-volatile memory. 

CANCEL 

Discards all changes made since the last 
permanent save operation. 

 

 

 

3.8

 

Parameter group 4: Messages 

 

 

 

3.8.1

 

TIME_OUT – Dead band time limit 

 

 

 
With this parameter you enter the monitoring time until 
reaching the setpoint. 
When the tolerance band is exceed ed, the monitoring time is 
started. If the tolerance band  within the prede

fi

ned time is 

again not reached by the new po sition setpoint, an alarm is 
triggered. 
(Parameter 

TIME_OUT

 in parameter group 5 must be 

activated.) 

 

CAUTION

With active shutdown function  there is no alarm message. 

 

Once the setpoint has been reached, the alarm is 
automatically reset. 
 

 

 

NOTE

 

The stroke time to be monitored should be 1.5 to 2x greater 
than the shortest stroke time  selected during automatic 
adjustment. 

 
Press and hold the 

ENTER

 button to display the stroke time. 

Press 

ENTER

 again to toggle between UP stroke time and 

DOWN stroke time. 

 

3.8.2

 

POS_SW1 – Switching point SW1 

 

 

 

With this parameter you can de

fi

ne the switching point SW1 as 

a percentage of the operating range. 
If the position is above or below SW1, the corresponding 
signal output on the plug-in  module is activated (see also 
parameter group 

DIG_OUT 

on page 29). 

 

NOTE

 

Changing the operating range also changes the positions of 
the switching points with respect to the position of the valves 
and 

fi

ttings. 

conf

mA

%

C

°

conf

mA

%

C

°

conf

c onf

mA

%

C

conf

mA

%

C

°

Содержание TZIDC

Страница 1: ...Con guration Parameterization Instruction COI TZIDC TZIDC 200 EN TZIDC TZIDC 200 Digital Positioner Software revision 5 0 VALVE ACCESSORIES CONTROLS...

Страница 2: ...ion Additional documentation on TZIDC TZIDC 200 is available to download free of charge at www abb com positioners Alternatively simply scan this code Manufacturer ABB Automation Products GmbH Process...

Страница 3: ...es 18 3 8 1 TIME_OUT Dead band time limit 18 3 8 2 POS_SW1 Switchin g point SW1 18 3 8 3 POS_SW2 Switchin g point SW2 19 3 8 4 SW1_ACTV Active direction SW1 19 3 8 5 SW2_ACTV Active direction SW2 19 3...

Страница 4: ...lection 30 3 14 2 EXIT Return to op erating level 30 3 15 Parameter group 11 Safe positi on 31 3 15 1 FAIL_POS Safe position 31 3 15 2 FACT_SET Fac tory setting 31 3 15 3 IP TYP Type of the I P module...

Страница 5: ...injury WARNING The signal word WARNING in dicates an imminent danger Failure to observe this informat ion may result in death or severe injury CAUTION The signal word CAUTION in dicates an imminent d...

Страница 6: ...s Symbol Description Operation or access is restricted Control loop is active The symbol is displayed when the positioner is in operating mode 1 0 CTRL_ADP adaptive control or 1 1 CTRL_FIX fixed contr...

Страница 7: ...d fittings could not be operated with reference conditions while the Auto Adjust function was in progress Since self optimization in A daptive Mode is subject to several factors during operatio n and...

Страница 8: ...0 140 2 5 Inhibiting operation Positioner operation can be inhibited completely or partially via the digital input and the FUNCTION parameter in parameter group 10 DIG_IN digital input This allows the...

Страница 9: ...ESSAGES Events P5 _ ALARMS Alarms P6 _ MAN_ADJ Manual adjustment P7 _ CTRL_PAR Control parameters P8 _ ANLG_OUT Analog output P9 _ DIG_OUT Digital output P10 _ DIG_IN Digital input P11 _ FS IP Factory...

Страница 10: ...b P4 1 POS_SW1 Position switch 1 0 0 0 0 0 1 0 0 1 W S t n i o p g n i h c t i w S P4 2 POS_SW2 Position switch 2 0 0 0 1 0 0 0 1 0 0 2 W S t n i o p g n i h c t i w S P4 3 SW1_ACTV L E B _ L L A F D...

Страница 11: ...ssage HI R U C _ H G I H R U C _ W O L R U C _ H G P8 4 RB_CHAR T C E R I D C L A C E R T C E R I D s r e t c a r a h c d e t r e v n o C r e t c a r a h c k c a b d a e R P8 5 TEST E N O N n o i t c...

Страница 12: ...element Stroke time for both directions Control parameters Offset for the I P module NOTE The mode and scope of the automatic adjustment function can be selected using parameter ADJ_MODE M10487 I 3 co...

Страница 13: ...g any errors the device displays the message RUN in the bottom line and a code number in the top line indicating the step that is currently being executed 10 Air is completely evacuated from actuator...

Страница 14: ...identification of the affected device in the system Following activation the device sends a signal on request under HART 7 The following signals are available Disable One time Continuous 3 5 6 EXIT Re...

Страница 15: ...mA 3 6 3 CHARACT Characteristic curve Use this parameter to select a function that adjusts the behavior of the positioner to the analog input signal according to a predefined course This linearizes th...

Страница 16: ...0 Controlling continues in the 100 position 3 6 7 RAMP UP Setpoint ramp up Here the stroke time for the actuator can be increased A setpoint change is not directly transferred to the positioner instea...

Страница 17: ...ured working range Use this parameter to specify the lower limit of the operating range CAUTION This function is only active in control mode In the event of a power supply fa ilure electric or pneumat...

Страница 18: ...odes on page 33 Selection NV_SAVE Saves settings in the non volatile memory CANCEL Discards all changes made since the last permanent save operation 3 8 Parameter group 4 Messages 3 8 1 TIME_OUT Dead...

Страница 19: ...s to be triggered for exceeding or falling below switching point SW2 EXCEED Message when exceeding switching point SW2 FALL_BEL Message when falling below switching point SW2 3 8 6 EXIT Return to oper...

Страница 20: ...ACTIVE Alarm not active 3 9 4 CTRLER Controller inactive You can use this parameter to speci fy signaling of an alarm via a digital output if the positioner is not active i e if the control mode is in...

Страница 21: ...permanent save operation 3 10 Parameter group 6 Manual adjustment 3 10 1 MIN_VR Operating range min Normally the operating range is determined automatically during Autoadjust A partial run of automat...

Страница 22: ...The set limit value is displayed for 2 seconds MIN_SAVE 3 10 3 ACTUATOR Actuator type With this parameter you can configure the positioner for operation on a linear actuator sensor range 30 or on a p...

Страница 23: ...ithm The following options can be selected STEM actuator bolt on the valve spindle LEVER actuator bolt on the potentiometer lever For detailed information about the position of the actuator bolt see t...

Страница 24: ...ved The KP value is the gain of th e controller Th e control speed and stability are influenced by th e KP value With higher KP values the control speed increases NOTE The control precision is n ot af...

Страница 25: ...th positioning directions up down For most actuators satisfactor y control behavior is achieved with offset values between 40 80 If in the event of setpoint changes the contro l behavior demonstrates...

Страница 26: ...cing the speed of the dead band approach TEST Test The test is used to activate the controller and you can check the effects of the changes to this parameter group e g by introducing setpoint changes...

Страница 27: ...process is indicated by the message NV_SAVE After saving a plausibility check is executed If an error occurs during the check or while saving the data cannot be saved and an error message is displaye...

Страница 28: ...ALRM_CUR Simulation of an alarm curr ent 3 8 mA or I 20 5 mA CURRENT Output of the current setpoint as current value via analog output All configurations and settings of the analog input and or output...

Страница 29: ...is running th e corresponding message see below flashes in the display NONE No function ALRM_ON Alarm is simulated DO active SW1_ON Reaching switching point 1 is simulated SW1 active SW2_ON Reaching...

Страница 30: ...on level is inhibited However local operation on the operating level is possible The positioner can be configured externally via LCI modem and PC When the operator tries to activate the configuration...

Страница 31: ...sitioner has to be installe d on a different actuator and subsequently reconfigured CAUTION Risk of injury For safety reasons after loading the factory settings you must check whether the I P module t...

Страница 32: ...standard HART 5 and HART 7 To select use the arrow keys or Squawk command A standardized HART 7 comma nd causes the bottom menu line in the HMI of the addressed device to flash This visual aid makes i...

Страница 33: ...is a malfunction in the position sensor In control mode The actuator is moved to the safe position On the configuration level The output is set to neutral until a button is pressed After approx 5 sec...

Страница 34: ...turned to the manufacturer for repair Error when verifying the checksum of the configuration data RAM The actuator is moved to the safe position After approx 5 seconds the positioner is automatically...

Страница 35: ...ode or the binary input is active The controller does not follow the setpoint Switch to control mode or switch off the binary input Positioning timed out The settling time needed exceeds the configure...

Страница 36: ...erefore partial Autoadjust cannot be run Data is saved in the non volatile memory Measuring range is exceeded Auto Adjust was automatically stopped Data factory settings are being loaded Less than 10...

Страница 37: ...etected send the positioner for repair Yes Start Autostroke and save the va lues Switch the positioner to operating mode 1 1 Is the position stable Yes Good job The work activities are completed No Sw...

Страница 38: ...art Autoadjust Save parameters and switch the positioner to operating mode 1 1 In case of error messages check the mechanical configuration Now is it working No Good job The work activities are comple...

Страница 39: ...Notes TZIDC TZIDC 200 COI TZIDC TZIDC 200 EN 39 Notes...

Страница 40: ...matter and illustrations contained therein Any reproduction disclosu re to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB Copyright...

Отзывы: