TZIDC, TZIDC-200
| COI/TZIDC/TZIDC-200-EN 19
3.8.3
POS_SW2 – Switching point SW2
With this parameter you can de
fi
ne the switching point SW2 as
a percentage of the operating range.
If the position is above or below SW2, the corresponding
signal output on the plug-in module is activated (see also
parameter group
DIG_OUT
on page 29).
NOTE
Changing the operating range also changes the positions of
the switching points with respect to the position of the valves
and
fi
ttings.
3.8.4
SW1_ACTV – Active direction SW1
With this parameter you de
fi
ne whether a message is to be
triggered for exceeding or falling below switching point SW1.
EXCEED
Message when exceeding switching point SW1.
FALL_BEL
Message when falling below switching point SW1.
3.8.5
SW2_ACTV – Active direction SW2
With this parameter you de
fi
ne whether a message is to be
triggered for exceeding or falling below switching point SW2.
EXCEED
Message when exceeding switching point SW2.
FALL_BEL
Message when falling below switching point SW2.
3.8.6
EXIT – Return to operating level
With this parameter you can leave the con
fi
guration level. The
positioner returns to the operating level. Here you can either
save data in the non-volatile me mory or discard all previously
made changes (also the changes in other parameter groups).
To leave the con
fi
guration level (with or without saving), press
and hold
ENTER
until the countdown from 3 to 0 is
fi
nished.
The active saving process is indicated by the message
NV_SAVE
. After saving a plausibility check is executed.
If an error occurs during the check or while saving, the data
cannot be saved and an error message is displayed instead
(see Chapter "Error codes" on page 33).
Selection
NV_SAVE
Saves settings in the non-volatile memory.
CANCEL
Discards all changes made since the last
permanent save operation.