Chapter 4: Maintenance
SynaG Series Installation Manual
65
Troubleshooting batteries
Battery supply and battery fuse faults are indicated by a flashing Supply Fault
LED. If this LED is flashing, check the following:
• That the battery cables are in good condition
• That the battery cables are connected securely and correctly at the battery
and at the control panel PCB
If the cables are in good condition and all connections are correct, then the
batteries should be replaced immediately.
Replacing batteries
Batteries must be replaced periodically as recommended by the battery
manufacturer. The useful life of the battery is approximately four years. Avoid the
total discharge of the batteries. Always use the recommended replacement
batteries.
To replace the batteries:
1. Disconnect and remove the existing batteries from the cabinet.
2. Install and connect the replacement batteries using the bridge provided.
Observe correct polarity.
3. Dispose of the batteries as required by local or regional regulations.
Содержание Kidde AirSense SynaG Series
Страница 1: ...SynaG Series Installation Manual P N 501 435003 1 10 REV 1 0 ISS 14OCT11 ...
Страница 6: ...iv SynaG Series Installation Manual ...
Страница 10: ...Chapter 1 Introduction 4 SynaG Series Installation Manual ...
Страница 72: ...Chapter 4 Maintenance 66 SynaG Series Installation Manual ...
Страница 82: ...Chapter 5 Technical specifications 76 SynaG Series Installation Manual Figure 23 Eight zone cabinet with cover ...
Страница 84: ...Chapter 5 Technical specifications 78 SynaG Series Installation Manual ...
Страница 96: ...Appendix A Configuration presets 90 SynaG Series Installation Manual ...
Страница 100: ...Appendix B Product compliance 94 SynaG Series Installation Manual ...
Страница 103: ......
Страница 104: ......