Chapter 3: Configuration and commissioning
44
SynaG Series Installation Manual
In the time between the end of the configured disable time and the end of the
configured sounder delay (when the Sounder Start/Stop LED is flashing),
pressing the Sounder Start/Stop button silences sounders (before activation).
A configured sounder delay may still be cancelled while the delay is running (and
sounders activated) by pressing the Sounder Delay button.
Use this menu to configure the time while sounders silence is disabled. The
default setting is 1 minute.
To configure the Sounders Silence Disabled Time:
1. Set the display as shown below, and then press Enter.
The Sounders Start/Stop LED flashes fast to indicate that the Sounders
Silence Disabled Time configuration menu is active.
2. Select a delay value from 1 to 10 minutes using the value selection buttons (2
and 4).
3. Press Enter.
4. Save your changes.
Zone configuration
Use this menu to configure zone settings for each zone in your fire alarm system.
The default setting for each operating mode is included in Appendix A
“Configuration presets” on page 79.
To configure the zone:
1. Set the display as shown below, and then press Enter.
2. Select the zone (for example, zone 1), and then press Enter.
The Zone fault/test/disable LED flashes fast to indicate that the corresponding
zone configuration menu is active.
3. Select a value using the value selection buttons (2 and 4).
4. Press Enter.
5. Save your changes.
The available settings for this feature are shown below.
Содержание Kidde AirSense SynaG Series
Страница 1: ...SynaG Series Installation Manual P N 501 435003 1 10 REV 1 0 ISS 14OCT11 ...
Страница 6: ...iv SynaG Series Installation Manual ...
Страница 10: ...Chapter 1 Introduction 4 SynaG Series Installation Manual ...
Страница 72: ...Chapter 4 Maintenance 66 SynaG Series Installation Manual ...
Страница 82: ...Chapter 5 Technical specifications 76 SynaG Series Installation Manual Figure 23 Eight zone cabinet with cover ...
Страница 84: ...Chapter 5 Technical specifications 78 SynaG Series Installation Manual ...
Страница 96: ...Appendix A Configuration presets 90 SynaG Series Installation Manual ...
Страница 100: ...Appendix B Product compliance 94 SynaG Series Installation Manual ...
Страница 103: ......
Страница 104: ......