Chapter 3: Configuration and commissioning
62
SynaG Series Installation Manual
Event Response
time
Network fault
Less than 100 seconds
Earth fault
Less than 100 seconds
Battery charger fault
Less than 100 seconds
No batteries found fault
Less than 3 minutes
Mains fault
Less than 3 minutes
Out of service fault
Less than 100 seconds
Fuse/protection fault
Less than 3 minutes
System fault
Less than 100 seconds
Battery high resistance fault
Less than 4 hours