35
Figure 58: Typical Facing Layout
c
LeaRances
& n
on
-c
ombustibLe
:
When installing as a zero clearance appliance the correct clearances and materials must be used.
a
bove
u
nit
:
The supplied noncombustible board is required above the unit up to 12” MIN.
However this not required if the Cool Surface System has been properly installed.
h
eaDeR
:
The header can be made up of wood 2x4 construction at or above the top standoffs.
b
eLow
u
nit
:
Is is recommended the appliance sit a solid and level piece of 3/4” plywood.
a
Djacent
/s
iDewaLL
:
There must be a minimum distance of 3 1/2” (89mm)
from the finishing edge of the
appliance to an adjacent wall composed of combustible material.
m
anteL
:
It is not necessary to install a mantel, but if one is desired the guidelines as shown in “
I
nItIal
I
nstallatIon
- M
antel
r
equIreMents
”.
F
LooR
:
The unit must be raised to accommodate flooring thickness. Always ensure convective air gaps
around the unit remain unobstructed. Combustible flooring can be used but
make sure to review the maximum
allowable temperature for your specific flooring material. Since every home and installation is unique, temperatures
should be verified at the time of install. A hearth should be installed if temperatures exceed the manufacturers
maximum allowable temperature.
Initial Installation
QUALIFIED INSTALLERS ONLY
2"
51mm
Minimum
42"
1067mm
Minimum
72 12 "
1842mm
Minimum
12"
305mm
1133mm
127mm
Maximum
Non-Combustible board NOT
mandatory for CSS Install
CSS Air Discharge
5"
37 58 "