Uponor SETPOINT 511S Скачать руководство пользователя страница 9

Sequence of Operation for the SetPoint 512 
(Heat and Cool) Controller

Use the DIP switch located on the circuit board inside the thermostat to

select the Heat and Cool mode of operation.

Air Sensor Only Operation

When operating with only an air sensor, the on times of the Heat 1 

relay and the Cool relay are calculated to satisfy the requirements of the 

air sensor.

Slab or Floor Sensor Only Operation

When operating with only a slab or floor sensor, the on time of the Heat 1

relay is calculated to satisfy the requirements of the slab or floor sensor.

The SetPoint 512 operates to maintain the slab or floor at the minimum

slab temperature setting.

Note:

When operating with only a slab or floor sensor, the Cool relay does

not operate. Operating with only a slab or floor sensor can lead to

either overheating or underheating of the space.

Air and Slab or Floor Sensor Operation

When operating the air and slab or floor sensors concurrently, the 

controller calculates an on time for the Heat 1 relay to satisfy the slab 

or floor sensor’s requirements and an on time to satisfy the air sensor’s

requirements. The Heat 1 relay operates for the longer of these two on

times. The controller also calculates an on time for the Cool relay to 

satisfy the air sensor’s requirements. In this situation, heating and cooling

can happen at the same time to prevent the space from overheating. 

This is most likely to occur when the slab is operating at the slab 

minimum temperature.

While the minimum slab temperature is satisfied, the Heat 1 relay on time 

is calculated to satisfy the air temperature setting. However, the maximum

slab temperature setting limits the Heat 1 relay on time when the slab 

temperature becomes too warm. In this situation, underheating can occur 

in the space.

13

Section 2 — Installation

Air Sensor Only Operation

When operating with only an air sensor, the on times for the Heat 1 and

Heat 2 relays are calculated to satisfy the requirements of the air sensor.

Slab or Floor Sensor Only Operation

When operating with only a slab or floor sensor, the on times for the Heat

1 and Heat 2 relays are calculated to satisfy the requirements of the slab or

floor sensor. The SetPoint 512 operates to maintain the slab or floor at the

minimum slab temperature setting.

Note:

Operating with only a slab or floor sensor can lead to either 

overheating or underheating of the space.

Air and Slab or Floor Sensor Operation

When operating the air and slab or floor sensors concurrently, the 

controller calculates an on time for the Heat 1 relay to satisfy the slab or

floor sensor’s requirements and on times for the Heat 1 and Heat 2 relays

to satisfy the air sensor’s requirements. The controller operates the Heat 1

relay for the longer of these two on times.

While the minimum slab or floor temperature is satisfied, the on times of

the Heat 1 and Heat 2 relays are calculated to satisfy the air temperature

requirements.

During heavy loads, the maximum slab or floor temperature setting limits

the on time of the Heat 1 relay. In this situation, the Heat 2 relay may be

on while the Heat 1 relay is off.

Note:

During light heating loads, overheating can occur due to the 

minimum slab or floor temperature requirements.

Mode 

Heat

In the Heat mode, the Heat 1 and Heat 2 relays satisfy the temperature

requirement of the zone.

Off

The Heat 1 and Heat 2 relays do not operate in the Off mode.

Note:

If an air, slab or floor sensor is active in the Off mode, a freeze-

protection function enables, allowing the relays to operate and 

keep the zone above 35°F (2°C).

12

Содержание SETPOINT 511S

Страница 1: ...739 Fax 952 891 1409 Web www uponor usa com E mail learnmore uponor usa com Uponor Ltd 655 Park Street Regina SK S4N 5N1 Tel 888 994 7726 Fax 800 638 9517 Web www uponor ca E mail info uponor ca INSTA...

Страница 2: ...SetPoint 512 Two stage Heat 11 Sequence of Operation for the SetPoint 512 Heat and Cool 13 Section 3 Navigating the Menus View Menu 15 Adjust Menu 15 Section 4 Troubleshooting Error Messages 21 Sectio...

Страница 3: ...oint 511s and 512 Controllers are microprocessor based controls that sense the air temperature in a specific area and increase the comfort level of that area as well as increase the energy efficiency...

Страница 4: ...into the small slot located in the top of the controller 2 Push the screwdriver against the plastic tab and pull the top of the front cover so that it pivots around the bottom edge of the base See Fi...

Страница 5: ...wer to the R and C terminals on the controller This connection provides power to the microprocessor and display of the controller 2 When wiring an optional sensor connect the two wires from the sensor...

Страница 6: ...7 6 Section 2 Installation Figure 7 Wiring the 512 Figure 7 Wiring the 511s 24VAC 24VAC 24VAC Wiring to 24VAC Zone Valve 24VAC VAC 24VAC 24VAC Figure 6 Wiring the Zone Control Module ZCM...

Страница 7: ...mperature in the zone that the controller is controlling The temperature the slab or floor sensor reads is used in the on time calculations for the Heat relay and allows the controller to operate the...

Страница 8: ...The SetPoint controllers feature two access levels User and Installer which restrict the number of items available in the display menus Change the access level via the DIP switch located on the circu...

Страница 9: ...hen the slab temperature becomes too warm In this situation underheating can occur in the space 13 Section 2 Installation Air Sensor Only Operation When operating with only an air sensor the on times...

Страница 10: ...ock In the Auto mode the cooling temperature is limited to 3 F 1 5 C above the heating temperature If the cooling temperature is set below the heating temperature the controller automatically adjusts...

Страница 11: ...ating the Menus ROOM HEAT This displays the desired temperature for heating must set active air sensor to Heat or Auto See Figure 19 35 to 100 F 2 to 38 C ROOM COOL 512 Only This displays the desired...

Страница 12: ...t or Auto See Figure 33 35 to 100 F 2 to 38 C OFF ROOM HEAT UnOcc This displays the desired heating temperature when the space is unoccupied Set the active air sensor to Heat or Auto See Figure 34 35...

Страница 13: ...nsor to INDR or SLAB After correcting the fault press any button to clear the error message See Figure 46 ROOM Shr The controller s internal air sensor has a short circuit This error cannot be repaire...

Страница 14: ...0 Hz 3 VA Relay 24VAC 2 A Latching Sensors NTC thermistor 10k 77 F 25 C 0 2 C 3892 Included Floor Sensor A3040079 Optional Outdoor Sensor A3060070 Universal Sensor A3060071 and Epoxy coated Slab Senso...

Страница 15: ...US meets ICES and FCC regulations for EMI RFI Ambient Indoor use only 32 to 122 F 0 to 50 C Conditions 90 RH non condensing Adjustment 34 to 122 F 1 to 50 C Range for Slab or Floor Setting Power Suppl...

Страница 16: ...Notes 26...