Mode

Auto

In the Auto mode, the controller automatically switches between heating

and cooling the space. However, the heating operation has priority over the

cooling operation. In this mode, the minimum slab or floor temperature is

maintained even when the controller is cooling the air.

Heat

In the Heat mode, the Heat 1 relay operates to satisfy the heating 

temperature requirement of the zone, and disable the cooling mode.

Cool

In the Cool mode, the Cool relay operates to satisfy the cooling temperature

requirement of the zone, and disable the heating mode. When using a slab

or floor sensor, the slab minimum temperature is ignored.

Off

In the Off mode, the Heat 1 and Cool relays do not operate.

Note:

If an air, slab or floor sensor is active in the Off mode, a freeze-

protection function enables, allowing the Heat 1 relay to operate

and keep the zone above 35°F (2°C).

Heating and Cooling Interlock

Time Interlock 

The SetPoint 512 features a Cooling Interlock setting to prevent frequent

changes between heating and cooling. Once the Heat 1 relay is off for a

minimum of one heating cycle or the length of the Cooling Interlock,

whichever is longer, cooling is permitted.

Temperature Interlock 

In the Auto mode, the cooling temperature is limited to 3°F (1.5°C) above

the heating temperature. If the cooling temperature is set below the heating

temperature, the controller automatically adjusts the cooling setpoint.

When operating in the Cool mode, there is no interlock between the 

heating and cooling temperature.

14

Section 3 

Navigating the Menus

View Menu

ROOM TARGET

This displays the current desired air temperature

for the space (one active air sensor required). This

is only available when in the Installer access level. 

(See 

Figure 14

.) 

ROOM

This displays the current air temperature for the 

space that is the average of all active air sensors

(one active air sensor required). (See 

Figure 15

.)

OUTDOOR

This displays the current temperature at the 

outdoor sensor. (See 

Figure 16

.)

Note:

SENS must be set to OUT.

SLAB

This displays the current slab or floor temperature

(one active air sensor required). If two slab or 

floor sensors are present, this is the average 

temperature. MIN is displayed when the slab or 

floor minimum temperature is calling for heat. 

The slab or floor sensor may call for heat even 

though the room setpoint temperature is satisfied. 

(See 

Figure 17

.)

Adjust Menu

MODE

This displays the current mode of operation of 

the thermostat. (See 

Figure 18

.)

OFF, HEAT (511s) or OFF, COOL, AUTO, 
HEAT (512)

15

Section 3 — Navigating the Menus

Figure 14

Figure 15

Figure 16

Figure 17

Figure 18

Содержание SETPOINT 511S

Страница 1: ...739 Fax 952 891 1409 Web www uponor usa com E mail learnmore uponor usa com Uponor Ltd 655 Park Street Regina SK S4N 5N1 Tel 888 994 7726 Fax 800 638 9517 Web www uponor ca E mail info uponor ca INSTA...

Страница 2: ...SetPoint 512 Two stage Heat 11 Sequence of Operation for the SetPoint 512 Heat and Cool 13 Section 3 Navigating the Menus View Menu 15 Adjust Menu 15 Section 4 Troubleshooting Error Messages 21 Sectio...

Страница 3: ...oint 511s and 512 Controllers are microprocessor based controls that sense the air temperature in a specific area and increase the comfort level of that area as well as increase the energy efficiency...

Страница 4: ...into the small slot located in the top of the controller 2 Push the screwdriver against the plastic tab and pull the top of the front cover so that it pivots around the bottom edge of the base See Fi...

Страница 5: ...wer to the R and C terminals on the controller This connection provides power to the microprocessor and display of the controller 2 When wiring an optional sensor connect the two wires from the sensor...

Страница 6: ...7 6 Section 2 Installation Figure 7 Wiring the 512 Figure 7 Wiring the 511s 24VAC 24VAC 24VAC Wiring to 24VAC Zone Valve 24VAC VAC 24VAC 24VAC Figure 6 Wiring the Zone Control Module ZCM...

Страница 7: ...mperature in the zone that the controller is controlling The temperature the slab or floor sensor reads is used in the on time calculations for the Heat relay and allows the controller to operate the...

Страница 8: ...The SetPoint controllers feature two access levels User and Installer which restrict the number of items available in the display menus Change the access level via the DIP switch located on the circu...

Страница 9: ...hen the slab temperature becomes too warm In this situation underheating can occur in the space 13 Section 2 Installation Air Sensor Only Operation When operating with only an air sensor the on times...

Страница 10: ...ock In the Auto mode the cooling temperature is limited to 3 F 1 5 C above the heating temperature If the cooling temperature is set below the heating temperature the controller automatically adjusts...

Страница 11: ...ating the Menus ROOM HEAT This displays the desired temperature for heating must set active air sensor to Heat or Auto See Figure 19 35 to 100 F 2 to 38 C ROOM COOL 512 Only This displays the desired...

Страница 12: ...t or Auto See Figure 33 35 to 100 F 2 to 38 C OFF ROOM HEAT UnOcc This displays the desired heating temperature when the space is unoccupied Set the active air sensor to Heat or Auto See Figure 34 35...

Страница 13: ...nsor to INDR or SLAB After correcting the fault press any button to clear the error message See Figure 46 ROOM Shr The controller s internal air sensor has a short circuit This error cannot be repaire...

Страница 14: ...0 Hz 3 VA Relay 24VAC 2 A Latching Sensors NTC thermistor 10k 77 F 25 C 0 2 C 3892 Included Floor Sensor A3040079 Optional Outdoor Sensor A3060070 Universal Sensor A3060071 and Epoxy coated Slab Senso...

Страница 15: ...US meets ICES and FCC regulations for EMI RFI Ambient Indoor use only 32 to 122 F 0 to 50 C Conditions 90 RH non condensing Adjustment 34 to 122 F 1 to 50 C Range for Slab or Floor Setting Power Suppl...