Uponor SETPOINT 511S Скачать руководство пользователя страница 8

Mode 

Heat

In the heat mode, the Heat relay satisfies the temperature requirement of

the zone.

Off 

The Heat relay does not operate in the Off mode.

Note:

If an air, slab or floor sensor is active in the Off mode, a freeze-

protection function enables, allowing the Heat relay to operate 

and keep the zone above 35°F (2°C).

Sequence of Operation for the SetPoint 512 
(Two-stage Heat) Controller

Select the two-stage mode of operation by using the DIP switch located on

the circuit board inside the SetPoint 512.

In cases where a one-stage heating system cannot provide sufficient heat

under all conditions, a second stage of heat is added to supplement the

first stage. Therefore, a two-stage system has one unit controlling two 

output relays.

Two-stage Logic

The temperature in a two-stage 

zone is controlled by varying the on

time of the Heat 1 and Heat 2 relays

during a cycle. Under light loads, the

Heat 1 relay is cycled on and off. As

the load increases, the Heat 1 relay

on time increases until it reaches the 

maximum of the cycle length. If using a slab or floor sensor, the Heat 1

relay on time increases until the temperature reaches the slab or floor 

maximum setting. The Heat 2 relay is then cycled, and the on time increases

as the load increases. When the heating load decreases, the on time of 

the Heat 2 relay reduces until the Heat 2 relay turns off completely. The

controller then reduces the on time of the Heat 1 relay. (See 

Figure 13

.)

Note:

When using a slab or floor sensor, the Heat 2 relay may be on while

the Heat 1 relay is off if the slab or floor temperature has reached

the slab maximum setting.

11

Section 2 — Installation

Access Levels

The SetPoint controllers feature two access 

levels — User and Installer — which restrict the

number of items available in the display menus.

Change the access level via the DIP switch

located on the circuit board inside the controller.

(See 

Figure 12

.)

The Installer access level allows the installer to

adjust all the settings in the controller including 

those required to match the controller to the 

mechanical system and devices. The User access level allows the end user 

to adjust the time, temperatures and schedules.

Note:

The SetPoint 512 features an additional DIP switch for selecting

between the two-stage heating or cooling modes.

Sequence of Operation for the SetPoint 511s 
Air Sensor Only Operation

When operating with only an air sensor, the on time for the Heat relay is

calculated to satisfy the requirements of the air sensor.

Slab or Floor Sensor Only Operation

When operating with only a slab or floor sensor, the on time for the 

Heat relay is calculated to satisfy the requirements of the slab or floor 

sensor. The controller operates to maintain the slab at the minimum slab

temperature setting.

Note:

Using only a slab or floor sensor may cause overheating or 

underheating of the space.

Air and Slab or Floor Sensor Operation

When operating with both air and slab or floor sensors, the controller 

calculates an on time for the Heat relay to satisfy the slab or floor sensor’s

requirements and an on time to satisfy the air sensor’s requirements. The

Heat relay operates for the longer of these two on times.

During light heating loads, overheating can occur due to the minimum 

slab or floor temperature requirements.

During heavy heating loads, the maximum slab or floor temperature 

setting limits the on time of the Heat relay. In this situation, underheating

can occur.

10

50

1s 

Figure 12: 
DIP Switch Location

Figure 13: Two-stage Logic

Содержание SETPOINT 511S

Страница 1: ...739 Fax 952 891 1409 Web www uponor usa com E mail learnmore uponor usa com Uponor Ltd 655 Park Street Regina SK S4N 5N1 Tel 888 994 7726 Fax 800 638 9517 Web www uponor ca E mail info uponor ca INSTA...

Страница 2: ...SetPoint 512 Two stage Heat 11 Sequence of Operation for the SetPoint 512 Heat and Cool 13 Section 3 Navigating the Menus View Menu 15 Adjust Menu 15 Section 4 Troubleshooting Error Messages 21 Sectio...

Страница 3: ...oint 511s and 512 Controllers are microprocessor based controls that sense the air temperature in a specific area and increase the comfort level of that area as well as increase the energy efficiency...

Страница 4: ...into the small slot located in the top of the controller 2 Push the screwdriver against the plastic tab and pull the top of the front cover so that it pivots around the bottom edge of the base See Fi...

Страница 5: ...wer to the R and C terminals on the controller This connection provides power to the microprocessor and display of the controller 2 When wiring an optional sensor connect the two wires from the sensor...

Страница 6: ...7 6 Section 2 Installation Figure 7 Wiring the 512 Figure 7 Wiring the 511s 24VAC 24VAC 24VAC Wiring to 24VAC Zone Valve 24VAC VAC 24VAC 24VAC Figure 6 Wiring the Zone Control Module ZCM...

Страница 7: ...mperature in the zone that the controller is controlling The temperature the slab or floor sensor reads is used in the on time calculations for the Heat relay and allows the controller to operate the...

Страница 8: ...The SetPoint controllers feature two access levels User and Installer which restrict the number of items available in the display menus Change the access level via the DIP switch located on the circu...

Страница 9: ...hen the slab temperature becomes too warm In this situation underheating can occur in the space 13 Section 2 Installation Air Sensor Only Operation When operating with only an air sensor the on times...

Страница 10: ...ock In the Auto mode the cooling temperature is limited to 3 F 1 5 C above the heating temperature If the cooling temperature is set below the heating temperature the controller automatically adjusts...

Страница 11: ...ating the Menus ROOM HEAT This displays the desired temperature for heating must set active air sensor to Heat or Auto See Figure 19 35 to 100 F 2 to 38 C ROOM COOL 512 Only This displays the desired...

Страница 12: ...t or Auto See Figure 33 35 to 100 F 2 to 38 C OFF ROOM HEAT UnOcc This displays the desired heating temperature when the space is unoccupied Set the active air sensor to Heat or Auto See Figure 34 35...

Страница 13: ...nsor to INDR or SLAB After correcting the fault press any button to clear the error message See Figure 46 ROOM Shr The controller s internal air sensor has a short circuit This error cannot be repaire...

Страница 14: ...0 Hz 3 VA Relay 24VAC 2 A Latching Sensors NTC thermistor 10k 77 F 25 C 0 2 C 3892 Included Floor Sensor A3040079 Optional Outdoor Sensor A3060070 Universal Sensor A3060071 and Epoxy coated Slab Senso...

Страница 15: ...US meets ICES and FCC regulations for EMI RFI Ambient Indoor use only 32 to 122 F 0 to 50 C Conditions 90 RH non condensing Adjustment 34 to 122 F 1 to 50 C Range for Slab or Floor Setting Power Suppl...

Страница 16: ...Notes 26...

Отзывы: