Section 5
Technical Data
SetPoint 511s
Literature
SetPoint 511s and 512 Controllers Installation
and Operation Manual
Control
Microprocessor PI control;
This is not a safety (limit) control.
Packaged Weight
0.54 lb. (245 g), Enclosure J, white PVC plastic
Dimensions
2
7
⁄
8
" H x 2
7
⁄
8
" W x
13
⁄
16
" D (73 x 73 x 21mm)
Approvals
CSA C US, meets ICES and FCC regulations for
EMI/RFI
Ambient
Indoor use only, 32 to 122°F (0 to 50°C),
Conditions
< 90% RH non-condensing
Adjustment
34 to 122°F (1 to 50°C)
Range for Slab
or Floor Setting
Power Supply
24VAC ±10% 60 Hz 3 VA
Relay
24VAC, 2 A, Latching
Sensors
NTC thermistor, 10k @ 77°F (25°C ±0.2°C) ß=3892
Included
Floor Sensor (A3040079)
Optional
Outdoor Sensor (A3060070),
Universal Sensor (A3060071) and
Epoxy-coated Slab Sensor (A3060072)
23
Section 5 — Technical Data
SENS Shr
The optional sensor has a short circuit. Locate
and repair the problem as described in the
appropriate sensor instruction sheet. After
correcting the fault, press any button to clear
the error message. (See
Figure 49
.)
SENS OPN
The optional sensor has an open circuit. Locate
and repair the problem as described in the
appropriate sensor instruction sheet. After
correcting the fault, press any button to clear
the error message. (See
Figure 50
.)
22
Figure 49
Figure 50
Figure 51: SetPoint 511s