ROOM COOL Sleep (512 Only)
This displays the desired cooling temperature
when sleeping. Set the active air sensor to
Heat or Auto. (See
Figure 40
.)
35 to 100°F (2 to 38°C, OFF)
SLAB MIN Wake
This displays the minimum slab or floor
temperature when waking up (active slab or
floor sensor required). (See
Figure 41
.)
OFF, 34 to 122°F (OFF, 1 to 50°C, OFF)
SLAB MIN UnOcc
This displays the minimum slab or floor
temperature when the space is unoccupied
(active slab or floor sensor required).
(See
Figure 42
.)
OFF, 34 to 122°F (OFF, 1 to 50°C, OFF)
SLAB MIN Occ
This displays the minimum slab or floor
temperature when the space is occupied (active
slab or floor sensor required). (See
Figure 43
.)
OFF, 34 to 122°F (OFF, 1 to 50°C, OFF)
SLAB MIN Sleep
This displays the minimum slab or floor
temperature when sleeping (active slab or
floor sensor required). (See
Figure 44
.)
OFF, 34 to 122°F (OFF, 1 to 50°C, OFF)
19
Section 3 — Navigating the Menus
ROOM HEAT WAKE
This displays the desired heating temperature
when waking up. Set the active air sensor to
Heat or Auto. (See
Figure 33
.)
35 to 100°F (2 to 38°C, OFF)
ROOM HEAT UnOcc
This displays the desired heating temperature
when the space is unoccupied. Set the active
air sensor to Heat or Auto. (See
Figure 34
.)
35 to 100°F (2 to 38°C, OFF)
ROOM HEAT Occ
This displays the desired heating temperature
when the space is occupied. Set the active air
sensor to Heat or Auto. (See
Figure 35
.)
35 to 100°F (2 to 38°C, OFF)
ROOM HEAT Sleep
This displays the desired heating temperature
when sleeping. Set the active air sensor to Heat
or Auto. (See
Figure 36
.)
35 to 100°F (2 to 38°C, OFF)
ROOM COOL Wake (512 Only)
This displays the desired cooling temperature
when waking up. Set the active air sensor to
Cool or Auto. (See
Figure 37
.)
35 to 100°F (2 to 38°C, OFF)
ROOM COOL UnOcc (512 Only)
This displays the desired cooling temperature
when the space is unoccupied. Set the active
air sensor to Cool or Auto. (See
Figure 38
.)
35 to 100°F (2 to 38°C, OFF)
ROOM COOL Occ (512 Only)
This displays the desired cooling temperature
when the space is occupied. Set the active air
sensor to Cool or Auto. (See
Figure 39
.)
35 to 100°F (2 to 38°C, OFF)
18
Figure 33
Figure 34
Figure 35
Figure 36
Figure 37
Figure 38
Figure 39
Figure 41
Figure 42
Figure 44
Figure 43
Figure 40