Carrying out Measurements

If the RN conductor resistance exceeds
19.99

, the measurement is interrupted. The

message "Attention (1) + Limit (2) + RN" is dis-
played.

If the RPE resistance of PE conductor exceeds
1999

, the message "Attention (1) + Limit (2)

+ RN" is displayed.

If a contact voltage UB is generated between N
and PE during the active measurement and ex-
ceeding the selected contact voltage limit UL,
the measurement is interrupted and the sym-
bol "UB>UL" (3) is displayed.

If a measurement has been interrupted due to
contact voltage limit UL excess, the symbol
"UB>UL" (3) disappears at the same time as the
mains plug has been disconnected from the
socket and connected to a socket in perfect
working condition. During data saving, the
UB>UL error will be saved.

Please also refer to Chapter 7.0

Option to save measurement results pressing
the key "Store" (19).

If the defective condition of a socket has to be
saved, first press the key “Start” (18). After the
acoustic alarm signal the key "Store" (19) may
be pressed.

6.2   Internal Mains Resistance Measurement

Short-Circuit Current Measurement

To obtain precise measurement results, switch
off all loads or disconnect them from the mains.

Connect the mains lead to the mains connector
(13) 

Select measurement function via the function
switch (17).

Select contact voltage limit by means of the key
“VC / UL”  (15) in display.

The socket is continuously monitored for per-
fect functioning. If the symbol (6) "reverse
mains plug” is displayed, the plug has to be tur-
ned or the connection N and L of the three-pole
test lead have to be reversed. If the symbol
“Socket Error” (5) is displayed, an internal
mains error exists. If the voltage between N and
PE exceeds the selected (50V/25V), "UB>UL"
(3) is displayed.

By touching the contact electrode (16) the
contact voltage limit (chapter 6.6)  may now be
tested. If the symbol "socket error " (5) is dis-
played, a PE-error exists.

Press key “Start” (18).

Wait for approx. 3 seconds, during this the dis-
play shows “-”

Read the measurement result on the display.

By pressing the key “Display” (23) you may now
select the different measurement variables (RI /
IPSC)

If the internal resistance exceeds 19.99 

, the

message "Attention (1) + Limit (2) " is display-
ed.

Also refer to chapter 7.0.

Possibility to store measurement results by
pressing the key „Store" (19).

If the defective condition of a socket has to be
saved, first press the key “Start” (18). After the
acoustic alarm signal the key "Store" (19) may
be pressed.

Содержание TELARIS LOOP

Страница 1: ...TELARIS LOOP UNITEST Instruction Manual Cat No 8978...

Страница 2: ...2...

Страница 3: ...ement 8 6 2 Internal Mains Resistance Measurement 9 6 3 RPE RN RL Measurement 10 6 4 AC Voltage Measurement VAC 11 6 5 Frequency Measurement f 11 6 6 Contact Electrode 11 7 0 Display Indications 12 8...

Страница 4: ...ST TELARIS LOOP is charac terised by the following features A unit designed to allow the user to quickly esta blish earth loop impedance mains internal resi stance and prospective short circuit curren...

Страница 5: ...or all tasks In order to avoid electrical shock the valid sa fety and VDE regulations regarding excessive contact voltages must receive the utmost atten tion when working with voltages exceeding 120V...

Страница 6: ...s well as for trouble shooting Simultaneously to measurement the instrument TELARIS LOOP determines by calculation the short circuitcurrent Theshort circuitcurrentmust be known to guarantee that an ex...

Страница 7: ...for mains lead Test lead 14 LCD 15 Key Vc UL 50V 25V 25V for medical and agricul tural uses 16 Contact electrode 17 Measurement function switch off ZL IPSC Loop impedance short circuit current RI IPSC...

Страница 8: ...e mains lead to the mains connector 13 Select the measurement function R via the fun ction switch 17 Connect the test cables mains plug to UUT socket by respecting correct polarity Set a voltage conta...

Страница 9: ...ement results switch off all loads or disconnect them from the mains Connect the mains lead to the mains connector 13 Select measurement function via the function switch 17 Select contact voltage limi...

Страница 10: ...ressing the key Display 23 you may now select between the different measure ment variables If a value exceeds the measurement limit the Attention symbol appears If this result is sel ected with the ke...

Страница 11: ...t the measure ment instrument from UUT Also refer to chapter 7 0 No possibility to store the measurement re sults 6 5 Frequency Measurement Never apply tvoltages exceeding 300V to input sockets Connec...

Страница 12: ...ceeded Contact voltage limit 50 V Resistance measurement Zl Ipsc ZL 2 88 Contact voltage limit 50 V Resistance measurement Zl Ipsc RL excessive 19 99 Measurement is interrupted Contact voltage limit 5...

Страница 13: ...surement result by pressing key Store 19 Upon completion of storing a short signal is au dible and the symbol M 11 appears in the display for memory location In case of a full memory the symbol M blin...

Страница 14: ...rom the OFF position to the de sired function If the Battery is almost dead the symbol 8 appears in the indication The piece of equipment works furthermore however without claim on retention of the sp...

Страница 15: ...tery cells Never throw a battery into a fire as this could lead to an explosion Never expose batteries to humi dity Please consider your environment when you dis pose of your used batteries They belon...

Страница 16: ...01 Ohm 20 199 9 Ohm 0 1 Ohm 5 rdg 5 Digit 200 Ohm 1 999 kOhm 1 Ohm Internal Resistance RI Range Resolution Tolerance 0 05 19 99 Ohm 0 01 Ohm 5 rdg 5 Digit Resistance Neutral Conductor RN Range Resolu...

Страница 17: ...z 0 1 Hz 1 rdg 2 Digit 400V RI 1 M Contact voltage detection UL 25V 25V 5 15 UL 50V 50V 5 15 For large mains voltage fluctuations during measurements the measurement error may increase Auto power off...

Страница 18: ...18...

Страница 19: ...oumis un contr le technique permanent Ces m mes quipements de contr le sont calibr s r guli rement l aide d appareils de r f rence calibr s selon les di rectives et normes en vigueur dans les laborato...

Страница 20: ...e with unda maged warranty label Any damage due to dropping or incorrect handling are not covered by the war ranty If the instrument shows failure following ex piration of warranty our service depart...