Ensure that apparatus is mounted securely. 

Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose of 
preventing  the  ingress  of  flammable  atmospheres.  Replacement  parts  shall  be  in  accordance  with  the 
manufacturer’s specifications.   

NOTE: The use of silicon sealant may inhibit the effectiveness of some types of leak detection equipment. 
Intrinsically safe components do not have to be isolated prior to working on them. 

3. Repair to intrinsically safe components

Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not 
exceed the permissible voltage and current permitted for the equipment in use.     

Intrinsically  safe  components  are  the  only  types  that  can  be  worked  on  while  live  in  the  presence  of  a 
flammable atmosphere. The test apparatus shall be at the correct rating.     

Replace components only with parts specified by the manufacturer. Other parts may result in the ignition of 
refrigerant in the atmosphere from a leak. 

4. Cabling

Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any 
other adverse environmental effects. The check shall also take into account the effects of aging or continual 
vibration from sources such as compressors or fans. 

5. Detection of flammable refrigerants

Under  no  circumstances  shall  potential  sources  of  ignition  be  used  in  the  searching  for  or  detection  of 
refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used.   

6. Leak detection methods

The  following  leak  detection  methods  are  deemed  acceptable  for  systems  containing  flammable 
refrigerants.     

Electronic  leak  detectors  shall  be  used  to  detect  flammable  refrigerants,  but  the  sensitivity  may  not  be 
adequate, or may need re-calibration. (Detection equipment shall be calibrated in a refrigerant-free area.) 
Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. Leak 
detection equipment shall be set   

at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed and the 
appropriate  percentage  of  gas  (25  %  maximum)  is  confirmed.    Leak    detection    fluids    are    suitable 
for    use    with    most    refrigerants    but    the    use    of    detergents  containing  chlorine  shall  be  avoided 
as the chlorine may react with the refrigerant and corrode the copper pipe-work.     

If a leak is suspected, all naked flames shall be removed / extinguished. 

If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the 
system, or isolated (by means of shut off valves) in a part of the system remote from the leak. Oxygen free 
nitrogen (OFN) shall then be purged through the system both before and during the brazing process. 

7.

Removal and evacuation

When  breaking  into  the  refrigerant  circuit  to  make  repairs  –  or  for  any  other  purpose  –  conventional 

Содержание UPC-8029

Страница 1: ...INSTRUCTIONS MANUAL UPC 8029 LOCAL AIR CONDITIONER Read and save these instructions for future reference...

Страница 2: ...Adjustment IV Control Setting V Drainage Instructions VI Maintenance VII Troubleshooting VIII Appendix Please read these instructions before use and repair The drawings provided in this manual may no...

Страница 3: ...in the use of flammable refrigerants 12 All working procedure that affects safety means shall only be carried by competent persons Notes The air conditioning is only suitable for indoor use and is not...

Страница 4: ...nd understand the hazards involved Children shall not play with the appliance Cleaning and maintenance shall not be made by children without supervision If the supply cord is damaged it must be replac...

Страница 5: ...e control panel beautiful and fashionable with high quality remote control It adopts a user friendly remote control design Air filtration capability Timing switch function Protection function of autom...

Страница 6: ...ht position and the air conditioning should be placed on a flat surface Do not install and use the air conditioning in the bathroom or other humid environments 1 1 Install the heat pipe assembly as sh...

Страница 7: ...mponents of the assembly 1 2 Install the window sealing plate assembly 1 3 Install the body 1 Move the machine with installed heat pipe and fittings before the window and the distance between the body...

Страница 8: ...Up Key 3 Down Key 4 Display Window 5 Fan Speed Selection Key 6 Mode Selection Key 7 Power Key When the machine is powered on for the first time the buzzer will play power on music and then the machine...

Страница 9: ...timing in the case of power off press the key to open timing Press the key when the timing symbol flashes press up and down key to select the required timing value Timing values can be set in 1 24 hou...

Страница 10: ...t to sewer or other drainage area to empty the water details see Drainage Instructions at the end of this chapter After the water is emptied the machine will automatically return to the original state...

Страница 11: ...water plug and tighten the drainage cover Notes 1 Restart the machine after the water plug and drainage cover are installed otherwise condensate water of the machine will flow to the floor or the car...

Страница 12: ...ing to remove the EVA filter screen as shown in the above figure 2 Put the EVA filter screen into warm water with neutral detergent about 40 104 and dry it in the shade after rinsing clean Unit Storag...

Страница 13: ...being used is suitable for use with flammable refrigerants i e non sparking adequately sealed or intrinsically safe 5 Presence of fire extinguisher If any hot work is to be conducted on the refrigerat...

Страница 14: ...safety checks and component inspection procedures If a fault exists that could compromise safety then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with If th...

Страница 15: ...cumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks A halide torch or any other detector using a naked flame shall not be used 6 Leak detectio...

Страница 16: ...not occur when using charging equipment Hoses or lines shall be as short as possible to minimise the amount of refrigerant contained in them Cylinders shall be kept upright Ensure that the refrigerat...

Страница 17: ...special cylinders for the recovery of refrigerant Cylinders shall be complete with pressure relief valve and associated shut off valves in good working order Empty recovery cylinders are evacuated an...

Страница 18: ...ditioning by yourself Unqualified repair will lead to failure of the warranty card and may cause damage to users or their properties Problems Reasons Solutions The air conditioning does not work There...

Страница 19: ...r The remote control is not aligned with the direction of the remote control receiver Batteries are dead Replace batteries Displays E1 The pipe temperature sensor is abnormal Check the pipe temperatur...

Страница 20: ...collection systems for used electrical and electronic products Please help us to conserve the environment we live in DECLARATION OF CONFORMITY Herewith Amiridis Savvidis S A states that this product c...

Отзывы: