background image

7

Ensure that you are using the correct refrigerant type 
before recharging the unit.

Charging any refrigerant other than the original charge 
type (R-134a) will impair machine operation and can even 
lead to a destruction of the compressors. The compressors 
operating with this refrigerant type are lubricated with a 

synthetic polyolester oil.

RISK OF EXPLOSION   

Never use air or a gas containing oxygen during leak tests to 

purge lines or to pressurise a machine. Pressurised air 

mixtures or gases containing oxygen can be the cause of 
an explosion. Oxygen reacts violently with oil and grease.

Never exceed the specified maximum operating pressures. 
Verify the allowable maximum high- and low-side test 
pressures by checking the instructions in this manual and 

the pressures given on the unit name plate.

Only use dry nitrogen for leak tests, possibly with an 

appropriate tracer gas.

Do not unweld or flamecut the refrigerant lines or any 
refrigerant circuit component until all refrigerant (liquid 
and vapour) has been removed from unit. Traces of vapour 
should be displaced with dry air nitrogen. Refrigerant in 
contact with an open flame produces toxic gases.

The necessary protection equipment must be available, 
and appropriate fire extinguishers for the system and the 
refrigerant type used must be within easy reach.

Do not siphon refrigerant.

Avoid contact with liquid refrigerant on the skin or 
splashing it into the eyes. Use safety goggles and gloves. 
Wash any spills from the skin with soap and water. If liquid 
refrigerant enters the eyes, immediately and abundantly 
flush the eyes with water and consult a doctor.

The accidental releases of the refrigerant, due to small 
leaks or significant discharges following the rupture of a 
pipe or an unexpected release from a relief valve, can 
cause frostbites and burns to personnel exposed. Do not 
ignore such injuries. Installers, owners and especially 
service engineers for these units must:
-   Seek medical attention before treating such injuries.
-   Have access to a first-aid kit, especially for treating 

eye injuries.

We recommend to apply standard EN 378-3 Annex 3.

Never apply an open flame or live steam to a refrigerant 
container. Dangerous overpressure can result. If it is 
necessary to heat refrigerant, use only warm water.

During refrigerant removal and storage operations follow 

applicable regulations. These regulations, permitting 

condi-tioning and recovery of halogenated hydrocarbons 
under optimum quality conditions for the products and 

optimum safety conditions for people, property and the 

environment are described in standard NF E29-795.

At least once a year thoroughly inspect the protection 

devices (valves, pressure switches). If the machine operates 
in a corrosive environment, inspect the protection devices 
more frequently. 

Regularly carry out leak tests and immediately repair 
any leaks.

Ensure regularly that the vibration levels remain accep-
table and close to those at the initial unit start-up.

Before opening a refrigerant circuit, purge and consult the 

pressure gauges.

Change the refrigerant when there are equipment failures, 
following a procedure as the one described in NF E29-795 
or carry out a refrigerant analysis in a specialist laboratory.

If the refrigerant circuit remains open for longer than a day 
after an intervention (such as a component replacement), 
the openings must be plugged and the circuit must be 
charged with nitrogen (inertia principle). The objective is 
to prevent penetration of atmospheric humidity and the 
resulting corrosion on the internal walls and on non-
protected steel surfaces.

1.4 - Repair safety considerations

It is compulsory to wear personal protection equipment. 

The insulation must be removed and warming up must be 
limited by using a wet cloth. 

Before opening the unit always ensure that the circuit has 
been purged.

If work on the evaporator is required, ensure that the piping 
from the compressor is no longer pressurised (as the valve 
is not leaktight in the compressor direction.)

All installation parts must be maintained by the personnel in 

charge, in order to avoid material deterioration and injuries 

to people. Faults and leaks must be repaired immediately. 
The authorized technician must have the responsibility to 
repair the fault immediately. Each time repairs have been 

carried out to the unit, the operation of the protection devices 

must be re-checked.

Comply with the regulations and recommendations in unit 

and HVAC installation safety standards, such as: EN 378, 
ISO 5149, etc.

If a leak occurs or if the refrigerant becomes contaminated 
(e.g. by a short circuit in a motor) remove the complete 
charge using a recovery unit and store the refrigerant in 
mobile containers.

Repair the leak detected and recharge the circuit with the 

total R-134a charge, as indicated on the unit name plate. 

Certain parts of the circuit can be isolated. Only charge 
liquid refrigerant R-134a at the liquid line.

Содержание Carrier Touchpilot 30XW-V

Страница 1: ...MAINTENANCE INSTRUCTIONS Variable Speed Water Cooled Liquid Chillers Variable Speed Water to Water Heat Pumps 30XW V 30XWHV Nominal cooling capacity 587 1741 kW Nominal heating capacity 648 1932 kW 5...

Страница 2: ...wiring 16 5 7 24 and 230 V power reserve for the user 16 6 APPLICATION DATA 16 6 1 Operating limits 16 6 2 Condenser side installation recommendation 16 6 3 Minimum chilled water flow 17 6 4 Maximum c...

Страница 3: ...lve 22 9 6 Pressure vessels 22 9 7 High pressure safety switch 23 9 8 Electronic expansion valve EXV 23 9 9 Moisture indicator 23 9 10 Filter drier 23 9 11 Sensors 23 9 12 Frequency variator 23 10 OPT...

Страница 4: ...the right place and direction on the unit The units can also be lifted with slings using only the designated lifting points marked on the unit Use slings or lifting beams with the correct capacity an...

Страница 5: ...and may cause heart irregularities unconsciousness or death Vapour is heavier than air and reduces the amount of oxygen available for breathing These products cause eye and skin irritation Decomposit...

Страница 6: ...witch it is necessary to recover the refrigerant charge these pressure switches are not installed on automatic valves Schraeder type If any maintenance operations are carried out on the unit lock the...

Страница 7: ...These regulations permitting condi tioning and recovery of halogenated hydrocarbons under optimum quality conditions for the products and optimum safety conditions for people property and the environ...

Страница 8: ...t to repair or recondition any safety devices when corrosion or build up of foreign material rust dirt scale etc is found within the valve body or mechanism If necessary replace the device Do not inst...

Страница 9: ...on an even surface maximum tolerance is 5 mm in both axes there is adequate space above the unit for air flow and to ensure access to the components the number of support points is adequate and that...

Страница 10: ...ng an installation consult the certified dimensional drawings supplied with the unit or available on request For the positioning of the fixing points weight distribution and centre of gravity coordina...

Страница 11: ...re of gravity coordinates refer to the dimensional drawings Condenser Evaporator Dimensions in mm A B C D E F 30XW V 30XWHV 1150 1997 1514 1164 4730 219 1 219 1 1280 1997 1514 1164 4730 219 1 219 1 14...

Страница 12: ...tonnes 186 186 257 250 172 172 172 164 157 Capacity control Touch Pilot inverter driven compressor electronic expansion valve EXV Minimum capacity 20 20 20 20 10 10 10 10 10 Evaporator Multi pipe floo...

Страница 13: ...380 421 Circuit B A 270 330 330 380 421 With option 81 A 540 660 710 760 842 Maximum power input with option 150B Circuit A kW 141 173 199 221 141 173 199 199 221 Circuit B kW 141 173 173 199 221 Wit...

Страница 14: ...with the unit 5 The factory installed disconnect switch es circuit breaker s is are of a type suitable for power interruption in accordance with EN 60947 3 corresponds to IEC 60947 3 6 The units are d...

Страница 15: ...l electricity supplier at once and ensure that the unit is not switched on until corrective measures have been taken 5 2 Voltage phase imbalance 100 x max deviation from average voltage Average voltag...

Страница 16: ...ort Evaporator pump control signal Condenser pump control signal This does not control condenser pump operation for this function add option 156 and flow switch Heating cooling change over Available a...

Страница 17: ...ondenser water flow rates are shown in the table in chapter 6 7 Evaporator and condenser water flow rates If the system flow is higher than the maximum unit flow rate select the option with one pass l...

Страница 18: ...ecessary to add a buffer water tank to the circuit in order to achieve the required volume The tank must itself be internally baffled in order to ensure proper mixing of the liquid water or brine Refe...

Страница 19: ...fewest elbows and horizontal pipe runs at different levels Below the main points to be checked for the connection Follow the water inlet and outlet connection direction shown on the unit Install manu...

Страница 20: ...es destabilisation of copper hydroxides and enlargement of particles Electric conductivity 10 600 S cm pH Ideal case pH neutral at 20 25 C 7 pH 8 7 2 Water connections The water connections are Victau...

Страница 21: ...slave units Water inlet Water outlet Water pumps for each unit included as standard for units with hydronic module Additional sensors for leaving water control to be connected to channel 1 of the slav...

Страница 22: ...signed for prolonged storage of 15 years under nitrogen charge with a temperature difference of 20 K per day 452000 cycles start ups with a maximum difference of 6 K between two neighbouring points in...

Страница 23: ...re switches with manual reset called PZH former DBK are backed up by high pressure switches that require resetting with a tool The high pressure switches that require resetting with a tool are called...

Страница 24: ...s the unit by communication bus to a building management system 580 1710 LON gateway 148D Two directional communication board complying with Lon Talk protocol Connects the unit by communication bus to...

Страница 25: ...of the connections at the compressor terminals requires special precautions Please refer to the chapter below 11 STANDARD MAINTENANCE Air conditioning equipment must be maintained by profes sional tec...

Страница 26: ...is included with the compressor This low pressure switch should be temporarily installed as a hard safety on the high pressure part of the compressor The purpose of this switch is to protect the compr...

Страница 27: ...e the fan if a replace fan alert warning is displayed in the alarm list For any other alarm or problem at the frequency variator contact the Carrier service department The frequency variators in the 3...

Страница 28: ...properly Unit ground wire has been connected Electrical circuit protection has been sized and installed properly All terminals are tight All chilled water valves are open All chilled water piping is...

Страница 29: ...nominal kW capacity for air conditioning 6 5 litres nominal kW capacity for process cooling Proper loop volume established Proper loop corrosion inhibitor included litres of Proper loop freeze protec...

Страница 30: ...30...

Страница 31: ...31...

Страница 32: ...es order No 13474 76 05 2013 Manufacturer Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the European Union www eurovent cer...

Отзывы: