background image

5

The relief valve must only be removed if the fire risk is 
fully controlled and after checking that this is allowed by 
local regulations and authorities. This is the responsibility 
of the operator.

When the unit is subjected to fire, safety devices prevent 
rupture due to over-pressure by releasing the refrigerant. 
The fluid may then be decomposed into toxic residues 
when subjected to the flame:
-  Stay away from the unit.
-  Set up warnings and recommendations for personnel in 

charge to stop the fire.

-  Fire extinguishers appropriate to the system and the 

refrigerant type must be easily accessible.

The external relief valves must in principle be connected 
to discharge pipes for units installed in a room. Refer to 
the installation regulations, for example those of European 

standards EN 378 and EN 13136.

They include a sizing method and examples for configura-
tion and calculation. Under certain conditions these stan-
dards permit connection of several valves to the same 
discharge pipe. Note: Like all other standards these EN 
standards are available from national standards organi-

sations. 

These pipes must be installed in a way that ensures that 
people and property are not exposed to refrigerant leaks. 
These fluids may be diffused in the air, but far away from 
any building air intake, or they must be discharged in a 
quantity that is appropriate for a suitably absorbing 

environment.

It is recommended to install an indicating device to show 

if part of the refrigerant has leaked from the valve. The 
presence of oil at the outlet orifice is a useful indicator 
that refrigerant has leaked. Keep this orifice clean to 
ensure that any leaks are obvious.

The calibration of a valve that has leaked is generally 
lower than its original calibration. The new calibration 
may affect the operating range. To avoid a nuisance 
tripping or leaks, replace or re-calibrate the valve.

Periodic check of the relief valves: See paragraph 1.3 
“Maintenance safety considerations”.

Provide a drain in the discharge circuit, close to each 
relief valve, to avoid an accumulation of condensate or 

rain water.

All refrigerant handling precautions must comply with 

local regulations.

Ensure good ventilation, as accumulation of refrigerant 
in an enclosed space can displace oxygen and cause 
asphyxiation or explosions.

Inhalation of high concentrations of vapour is harmful 
and may cause heart irregularities, unconsciousness, or 

death. Vapour is heavier than air and reduces the amount 

of oxygen available for breathing. These products cause 

eye and skin irritation. Decomposition products are 

hazardous.

1.2 - Equipment and components under pressure

These products incorporate equipment or components under 

pressure, manufactured by Carrier or other manufacturers. 

We recommend that you consult your appropriate national 
trade association or the owner of the equipment or compo-

nents under pressure (declaration, re-qualification, retesting, 

etc.). The characteristics of this equipment/these components 
are given on the nameplate or in the required documenta-

tion, supplied with the products.

The units are intended to be stored and operate in an 
environment where the ambient temperature must not be 
less than the lowest allowable temperature indicated on 
the nameplate.

See section “9.6 - Pressure vessels”.

1.3 - Maintenance safety considerations

Carrier recommends the following drafting for a logbook 
(the table below should not be considered as reference 

and does not involve Carrier responsibility):

Intervention

Name of the 

commissioning 

engineer

Applicable 

national 

regulations

Verification 

Organism

Date

Nature

 (1)

(1)   Maintenance, repairs, regular verifications (EN 378), leakage, etc.

Engineers working on the electric or refrigeration compo-

nents must be authorized, trained and fully qualified to do so.

All refrigerant circuit repairs must be carried out by a trained 

person, fully qualified to work on these units. He must have 

been trained and be familiar with the equipment and the 
installation. All welding operations must be carried out by 

qualified specialists.

The insulation must be removed and heat generation must 
be limited by using a wet cloth.

Any manipulation (opening or closing) of a shut-off valve 
must be carried out by a qualified and authorised engineer. 
These procedures must be carried out with the unit shut-

down.

NOTE: The unit must never be left shut down with the 
liquid line valve closed, as liquid refrigerant can be trapped 
between this valve and the expansion device. (This valve 
is situated on the liquid line before the filter drier box.)

During any handling, maintenance and service operations 
the engineers working on the unit must be equipped with 
safety gloves, glasses, shoes and protective clothing.

Never work on a unit that is still energized. 

Never work on any of the electrical components, until the 
general power supply to the unit has been cut using the 
disconnect switch(es) in the control box(es). 

Содержание Carrier Touchpilot 30XW-V

Страница 1: ...MAINTENANCE INSTRUCTIONS Variable Speed Water Cooled Liquid Chillers Variable Speed Water to Water Heat Pumps 30XW V 30XWHV Nominal cooling capacity 587 1741 kW Nominal heating capacity 648 1932 kW 5...

Страница 2: ...wiring 16 5 7 24 and 230 V power reserve for the user 16 6 APPLICATION DATA 16 6 1 Operating limits 16 6 2 Condenser side installation recommendation 16 6 3 Minimum chilled water flow 17 6 4 Maximum c...

Страница 3: ...lve 22 9 6 Pressure vessels 22 9 7 High pressure safety switch 23 9 8 Electronic expansion valve EXV 23 9 9 Moisture indicator 23 9 10 Filter drier 23 9 11 Sensors 23 9 12 Frequency variator 23 10 OPT...

Страница 4: ...the right place and direction on the unit The units can also be lifted with slings using only the designated lifting points marked on the unit Use slings or lifting beams with the correct capacity an...

Страница 5: ...and may cause heart irregularities unconsciousness or death Vapour is heavier than air and reduces the amount of oxygen available for breathing These products cause eye and skin irritation Decomposit...

Страница 6: ...witch it is necessary to recover the refrigerant charge these pressure switches are not installed on automatic valves Schraeder type If any maintenance operations are carried out on the unit lock the...

Страница 7: ...These regulations permitting condi tioning and recovery of halogenated hydrocarbons under optimum quality conditions for the products and optimum safety conditions for people property and the environ...

Страница 8: ...t to repair or recondition any safety devices when corrosion or build up of foreign material rust dirt scale etc is found within the valve body or mechanism If necessary replace the device Do not inst...

Страница 9: ...on an even surface maximum tolerance is 5 mm in both axes there is adequate space above the unit for air flow and to ensure access to the components the number of support points is adequate and that...

Страница 10: ...ng an installation consult the certified dimensional drawings supplied with the unit or available on request For the positioning of the fixing points weight distribution and centre of gravity coordina...

Страница 11: ...re of gravity coordinates refer to the dimensional drawings Condenser Evaporator Dimensions in mm A B C D E F 30XW V 30XWHV 1150 1997 1514 1164 4730 219 1 219 1 1280 1997 1514 1164 4730 219 1 219 1 14...

Страница 12: ...tonnes 186 186 257 250 172 172 172 164 157 Capacity control Touch Pilot inverter driven compressor electronic expansion valve EXV Minimum capacity 20 20 20 20 10 10 10 10 10 Evaporator Multi pipe floo...

Страница 13: ...380 421 Circuit B A 270 330 330 380 421 With option 81 A 540 660 710 760 842 Maximum power input with option 150B Circuit A kW 141 173 199 221 141 173 199 199 221 Circuit B kW 141 173 173 199 221 Wit...

Страница 14: ...with the unit 5 The factory installed disconnect switch es circuit breaker s is are of a type suitable for power interruption in accordance with EN 60947 3 corresponds to IEC 60947 3 6 The units are d...

Страница 15: ...l electricity supplier at once and ensure that the unit is not switched on until corrective measures have been taken 5 2 Voltage phase imbalance 100 x max deviation from average voltage Average voltag...

Страница 16: ...ort Evaporator pump control signal Condenser pump control signal This does not control condenser pump operation for this function add option 156 and flow switch Heating cooling change over Available a...

Страница 17: ...ondenser water flow rates are shown in the table in chapter 6 7 Evaporator and condenser water flow rates If the system flow is higher than the maximum unit flow rate select the option with one pass l...

Страница 18: ...ecessary to add a buffer water tank to the circuit in order to achieve the required volume The tank must itself be internally baffled in order to ensure proper mixing of the liquid water or brine Refe...

Страница 19: ...fewest elbows and horizontal pipe runs at different levels Below the main points to be checked for the connection Follow the water inlet and outlet connection direction shown on the unit Install manu...

Страница 20: ...es destabilisation of copper hydroxides and enlargement of particles Electric conductivity 10 600 S cm pH Ideal case pH neutral at 20 25 C 7 pH 8 7 2 Water connections The water connections are Victau...

Страница 21: ...slave units Water inlet Water outlet Water pumps for each unit included as standard for units with hydronic module Additional sensors for leaving water control to be connected to channel 1 of the slav...

Страница 22: ...signed for prolonged storage of 15 years under nitrogen charge with a temperature difference of 20 K per day 452000 cycles start ups with a maximum difference of 6 K between two neighbouring points in...

Страница 23: ...re switches with manual reset called PZH former DBK are backed up by high pressure switches that require resetting with a tool The high pressure switches that require resetting with a tool are called...

Страница 24: ...s the unit by communication bus to a building management system 580 1710 LON gateway 148D Two directional communication board complying with Lon Talk protocol Connects the unit by communication bus to...

Страница 25: ...of the connections at the compressor terminals requires special precautions Please refer to the chapter below 11 STANDARD MAINTENANCE Air conditioning equipment must be maintained by profes sional tec...

Страница 26: ...is included with the compressor This low pressure switch should be temporarily installed as a hard safety on the high pressure part of the compressor The purpose of this switch is to protect the compr...

Страница 27: ...e the fan if a replace fan alert warning is displayed in the alarm list For any other alarm or problem at the frequency variator contact the Carrier service department The frequency variators in the 3...

Страница 28: ...properly Unit ground wire has been connected Electrical circuit protection has been sized and installed properly All terminals are tight All chilled water valves are open All chilled water piping is...

Страница 29: ...nominal kW capacity for air conditioning 6 5 litres nominal kW capacity for process cooling Proper loop volume established Proper loop corrosion inhibitor included litres of Proper loop freeze protec...

Страница 30: ...30...

Страница 31: ...31...

Страница 32: ...es order No 13474 76 05 2013 Manufacturer Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the European Union www eurovent cer...

Отзывы: