background image

20

Carrier recommendations on heat exchange fluids:

• 

No NH

4+

 ammonium ions in the water, they are very 

detrimental for copper. This is one of the most impor-
tant factors for the operating life of copper piping. A 
content of several tenths of mg/l will badly corrode the 
copper over time.

• 

Cl

-

 Chloride ions are detrimental for copper with a risk 

of perforations by corrosion by puncture. If possible 
keep below 125 mg/l.

• 

SO

4

2-

 sulphate ions can cause perforating corrosion, if 

their content is above 30 mg/l.

• 

No fluoride ions (<0.1 mg/l).

• 

No Fe

2+

 and Fe

3+

 ions with non negligible levels of 

dis-solved oxygen must be present. Dissolved iron < 5 
mg/l with dissolved oxygen < 5 mg/l.

• 

Dissolved silicon: silicon is an acid element of water 
and can also lead to corrosion risks. Content < 1 mg/l.

• 

Water hardness: > 0.5 mmol/l. Values between 1 and 

2.5 can be recommended. This will facilitate scale deposit 
that can limit corrosion of copper. Values that are too 
high can cause piping blockage over time. A total 
alkalimetric titre (TAC) below 100 mg/l is desirable.

• 

Dissolved oxygen: Any sudden change in water 

oxy-genation conditions must be avoided. It is as 
detrimen-tal to deoxygenate the water by mixing it 
with inert gas as it is to over-oxygenate it by mixing it 
with pure oxygen. The disturbance of the oxygenation 
conditions encourages destabilisation of copper 
hydroxides and enlargement of particles.

• 

Electric conductivity 10-600µS/cm.

• 

pH: Ideal case pH neutral at 20-25°C

 

7 < pH < 8

7.2 - Water connections

The water connections are Victaulic type connections. The inlet and outlet connection diameters are identical.

Inlet/outlet diameters

Evaporator 30XW-V/30XWHV

580

630

810

880

1150

1280

1470

1570

1710

Units without option 100C

Connection

in

6

6

8

8

8

8

8

8

8

Outside diameter

mm

168.3

168.3

219.1

219.1

219.1

219.1

219.1

219.1

219.1

Units with option 100C

Connection

in

6

6

8

8

8

8

8

8

8

Outside diameter

mm

168.3

168.3

219.1

219.1

219.1

219.1

219.1

219.1

219.1

Condenser 30XW-V/30XWHV

580

630

810

880

1150

1280

1470

1570

1710

Units without option 102C

Connection

in

6

6

8

8

8

8

8

8

8

Outside diameter

mm

168.3

168.3

219.1

219.1

219.1

219.1

219.1

219.1

219.1

Units with option 102C

Connection

in

8

8

8

8

8

8

8

8

8

Outside diameter

mm

219.1

219.1

219.1

219.1

219.1

219.1

219.1

219.1

219.1

If the water circuit must be emptied for longer than one 

month, the complete circuit must be placed under nitrogen 

charge to avoid any risk of corrosion by differential aeration.

ATTENTION: Filling, completing and draining the water 
circuit charge must be done by qualified personnel, using the 
air purges and materials that are suitable for the products. 

Charging and removing heat exchange fluids should be 
done with devices that must be included on the water 
circuit by the installer. Never use the unit heat exchangers 
to add heat exchange fluid.

Содержание Carrier Touchpilot 30XW-V

Страница 1: ...MAINTENANCE INSTRUCTIONS Variable Speed Water Cooled Liquid Chillers Variable Speed Water to Water Heat Pumps 30XW V 30XWHV Nominal cooling capacity 587 1741 kW Nominal heating capacity 648 1932 kW 5...

Страница 2: ...wiring 16 5 7 24 and 230 V power reserve for the user 16 6 APPLICATION DATA 16 6 1 Operating limits 16 6 2 Condenser side installation recommendation 16 6 3 Minimum chilled water flow 17 6 4 Maximum c...

Страница 3: ...lve 22 9 6 Pressure vessels 22 9 7 High pressure safety switch 23 9 8 Electronic expansion valve EXV 23 9 9 Moisture indicator 23 9 10 Filter drier 23 9 11 Sensors 23 9 12 Frequency variator 23 10 OPT...

Страница 4: ...the right place and direction on the unit The units can also be lifted with slings using only the designated lifting points marked on the unit Use slings or lifting beams with the correct capacity an...

Страница 5: ...and may cause heart irregularities unconsciousness or death Vapour is heavier than air and reduces the amount of oxygen available for breathing These products cause eye and skin irritation Decomposit...

Страница 6: ...witch it is necessary to recover the refrigerant charge these pressure switches are not installed on automatic valves Schraeder type If any maintenance operations are carried out on the unit lock the...

Страница 7: ...These regulations permitting condi tioning and recovery of halogenated hydrocarbons under optimum quality conditions for the products and optimum safety conditions for people property and the environ...

Страница 8: ...t to repair or recondition any safety devices when corrosion or build up of foreign material rust dirt scale etc is found within the valve body or mechanism If necessary replace the device Do not inst...

Страница 9: ...on an even surface maximum tolerance is 5 mm in both axes there is adequate space above the unit for air flow and to ensure access to the components the number of support points is adequate and that...

Страница 10: ...ng an installation consult the certified dimensional drawings supplied with the unit or available on request For the positioning of the fixing points weight distribution and centre of gravity coordina...

Страница 11: ...re of gravity coordinates refer to the dimensional drawings Condenser Evaporator Dimensions in mm A B C D E F 30XW V 30XWHV 1150 1997 1514 1164 4730 219 1 219 1 1280 1997 1514 1164 4730 219 1 219 1 14...

Страница 12: ...tonnes 186 186 257 250 172 172 172 164 157 Capacity control Touch Pilot inverter driven compressor electronic expansion valve EXV Minimum capacity 20 20 20 20 10 10 10 10 10 Evaporator Multi pipe floo...

Страница 13: ...380 421 Circuit B A 270 330 330 380 421 With option 81 A 540 660 710 760 842 Maximum power input with option 150B Circuit A kW 141 173 199 221 141 173 199 199 221 Circuit B kW 141 173 173 199 221 Wit...

Страница 14: ...with the unit 5 The factory installed disconnect switch es circuit breaker s is are of a type suitable for power interruption in accordance with EN 60947 3 corresponds to IEC 60947 3 6 The units are d...

Страница 15: ...l electricity supplier at once and ensure that the unit is not switched on until corrective measures have been taken 5 2 Voltage phase imbalance 100 x max deviation from average voltage Average voltag...

Страница 16: ...ort Evaporator pump control signal Condenser pump control signal This does not control condenser pump operation for this function add option 156 and flow switch Heating cooling change over Available a...

Страница 17: ...ondenser water flow rates are shown in the table in chapter 6 7 Evaporator and condenser water flow rates If the system flow is higher than the maximum unit flow rate select the option with one pass l...

Страница 18: ...ecessary to add a buffer water tank to the circuit in order to achieve the required volume The tank must itself be internally baffled in order to ensure proper mixing of the liquid water or brine Refe...

Страница 19: ...fewest elbows and horizontal pipe runs at different levels Below the main points to be checked for the connection Follow the water inlet and outlet connection direction shown on the unit Install manu...

Страница 20: ...es destabilisation of copper hydroxides and enlargement of particles Electric conductivity 10 600 S cm pH Ideal case pH neutral at 20 25 C 7 pH 8 7 2 Water connections The water connections are Victau...

Страница 21: ...slave units Water inlet Water outlet Water pumps for each unit included as standard for units with hydronic module Additional sensors for leaving water control to be connected to channel 1 of the slav...

Страница 22: ...signed for prolonged storage of 15 years under nitrogen charge with a temperature difference of 20 K per day 452000 cycles start ups with a maximum difference of 6 K between two neighbouring points in...

Страница 23: ...re switches with manual reset called PZH former DBK are backed up by high pressure switches that require resetting with a tool The high pressure switches that require resetting with a tool are called...

Страница 24: ...s the unit by communication bus to a building management system 580 1710 LON gateway 148D Two directional communication board complying with Lon Talk protocol Connects the unit by communication bus to...

Страница 25: ...of the connections at the compressor terminals requires special precautions Please refer to the chapter below 11 STANDARD MAINTENANCE Air conditioning equipment must be maintained by profes sional tec...

Страница 26: ...is included with the compressor This low pressure switch should be temporarily installed as a hard safety on the high pressure part of the compressor The purpose of this switch is to protect the compr...

Страница 27: ...e the fan if a replace fan alert warning is displayed in the alarm list For any other alarm or problem at the frequency variator contact the Carrier service department The frequency variators in the 3...

Страница 28: ...properly Unit ground wire has been connected Electrical circuit protection has been sized and installed properly All terminals are tight All chilled water valves are open All chilled water piping is...

Страница 29: ...nominal kW capacity for air conditioning 6 5 litres nominal kW capacity for process cooling Proper loop volume established Proper loop corrosion inhibitor included litres of Proper loop freeze protec...

Страница 30: ...30...

Страница 31: ...31...

Страница 32: ...es order No 13474 76 05 2013 Manufacturer Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the European Union www eurovent cer...

Отзывы: