background image

-6-

VENTING REQUIREMENTS

•  INSTALL VENT AT CLEARANCES SPECIFIED BY THE VENT MANUFACTURER.

• 

DO NOT CONNECT THE PELLET VENT TO A VENT SERVING ANY OTHER APPLIANCE OR STOVE.

• 

DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING SYSTEM OF THIS UNIT.

The following installation guidelines must be followed to ensure conformity with both the safety listing of this stove 

and to local building codes. Do not use makeshift methods or compromise in the installation.

MAXIMUM VENTING DISTANCE

Installation MUST include at least 3-feet of vertical pipe outside the home. This will create some natural draft to 

reduce the possibility of smoke or odor during appliance shutdown and keep exhaust from causing a nuisance 

or hazard by exposing people or shrubs to high temperatures. The maximum recommend vertical venting height 

is 12-feet for 3-inch type “PL” vent. Total length of horizontal vent must not exceed 4-feet. This could cause back 

pressure. Use no more than 180 degrees of elbows (two 90-degree elbows, or two 45-degree and one 90-degree 

elbow, etc.) to maintain adequate draft.

IMPORTANCE OF PROPER DRAFT

Draft is the force which moves air from the appliance up through the chimney. The amount of draft in your 

chimney depends on the length of the chimney, local geography, nearby obstructions and other factors. Too 

much draft may cause excessive temperatures in the appliance. Inadequate draft may cause backpuffing into 

the room and ‘plugging’ of the chimney.

Inadequate draft will cause the appliance to leak smoke into the room through appliance and chimney 

connector joints.

An uncontrollable burn or excessive temperature indicates excessive draft.

Take into account the chimney’s location to insure it is not too close to neighbors or in a valley which may cause 

unhealthy or nuisance conditions.

PELLET VENT TYPE

A UL listed 3-inch or 4-inch type “PL” pellet vent exhaust system must be used for installation and attached to the 

pipe connector provided on the back of the stove (use a 3-inch to 4-inch adapter for 4-inch pipe). Connection 

at back of stove must be sealed using Hi-Temp RTV. Use 4-inch vent if the vent height is over 12-feet or if the 

installation is over 2,500 feet above sea level.

We recommend the use of Simpson Dura-Vent® or Metal-Fab® pipe (if you use other pipe, consult your local 

building codes and/or building inspectors). Do not use Type-B Gas Vent pipe or galvanized pipe with this unit. The 

pellet vent pipe is designed to disassemble for cleaning and should be checked several times during the burning 

season. Pellet vent pipe is not furnished with the unit and must be purchased separately.

PELLET VENT INSTALLATION

The installation must include a clean-out tee to enable collection of fly ash and to permit periodic cleaning of the 

exhaust system. 90-degree elbows accumulate fly ash and soot thereby reducing exhaust flow and performance 

of the stove. Each elbow or tee reduces draft potential by 30% to 50%.

All joints in the vent system must be fastened by at least 3 screws, and all joints must be sealed with Hi-Temp 

RTV silicone sealant to be airtight. The area where the vent pipe penetrates to the exterior of the home must be 

sealed with silicone or other means to maintain the vapor barrier between the exterior and the interior of the 

home.

Vent surfaces can get hot enough to cause burns if touched by children. Noncombustible shielding or guards 

may be required.

PELLET VENT TERMINATION

Do not terminate the vent in an enclosed or semi-enclosed area, such as; carport, garage, attic, crawl space, 

under a sun deck or porch, narrow walkway, or any other location that can build up a concentration of fumes. 

The termination must exhaust above the outside air inlet elevation. The termination must not be located where it 

will become plugged by snow or other materials. Do not terminate the venting into an existing steel or masonry 

chimney.

IMPORTANT! This unit is equipped with a negative draft system that pulls air through the burn pot and pushes 

the exhaust out of the dwelling. If this unit is connected to a flue system other than the way explained in this 

manual, it will not function properly.

Содержание ASHLEY AP130

Страница 1: ...URE REFERENCE United States Stove Company 227 Industrial Park Road South Pittsburg TN 37380 Please read this entire manual before installation and use of this appliance Failure to follow these instruc...

Страница 2: ...The closed container of ashes should be placed on a non combustible surface or on the ground well away from all combustible materials pending final disposal The exhaust system should be checked monthl...

Страница 3: ...no greater than 1 5 not less than 8 200 BTU lb moisture under 8 by weight ash under 1 by weight and salt under 300 parts per million Pellets that are soft contain excessive amounts of loose sawdust h...

Страница 4: ...an NFI certified specialist IMPROPER INSTALLATION The manufacturer will not be held responsible for damage caused by the malfunction of a stove due to improper venting or installation Call 800 750 272...

Страница 5: ...m CORNER D Adjacent wall to unit 8 00 203mm ALCOVE E Alcove depth 36 00 914mm 5500 M only F Alcove height 60 00 520mm CLEARANCES Your pellet stove has been tested and listed for installation in reside...

Страница 6: ...the stove use a 3 inch to 4 inch adapter for 4 inch pipe Connection at back of stove must be sealed using Hi Temp RTV Use 4 inch vent if the vent height is over 12 feet or if the installation is over...

Страница 7: ...ith a kit that will handle most of this installation which will include a wall thimble that will allow the proper clearance through a combustible wall Once outside the structure a 3 in 76mm clearance...

Страница 8: ...g of the detector when reloading In addition to the previously detailed installation requirements mobile home installations must meet the following requirements The heater must be permanently bolted t...

Страница 9: ...er of this manual Because a forced draft pressure is required for the combustion process inside your stove it is extremely important that the exhaust system be properly installed and maintained And th...

Страница 10: ...at will not properly control the unit When adjusting the Draft Fan setting try only 1 setting above or below the heat setting It is better to leave the stove in the automatic mode ROOM FAN The room fa...

Страница 11: ...the preselected desired heat range setting 1 to 5 and the minimum heat range setting of 1 The T Stat will not turn the stove on and off When the desired room temperature has been reached and the T Sta...

Страница 12: ...4 Auger Output Test The display will show augr The auger motor is turned on full If the Auger Fuse is not blown and the fuse detection circuit is functioning the Heat Range LED will be lit and the ot...

Страница 13: ...urely closed the safety pressure switch will not allow the stove to feed fuel if there is no draft pressure inside the stove 7 Press the ON button on the control pad and set the heat Setting to your d...

Страница 14: ...ON button on the digital control panel your stove will begin to feed fuel and automatically start within 5 minutes TAMPER WARNING This wood heater has a manufacturer set minimum low burn rate that mus...

Страница 15: ...this could damage the glass DO NOT abuse the door glass by striking slamming or similar trauma Do not operate the stove with the glass removed cracked or broken FALL START UP Prior to starting the fir...

Страница 16: ...s down Hopper is empty refill the hopper Loss of draft pressure Make sure that the viewing door is closed and sealed properly If not adjust door catch and or replace door gaskets Check that all outsid...

Страница 17: ...g the lighting stage Quickly changes twice per second Flashing Heat Range Setting Indicator This indicates that the stove is in normal operation and that an over temperature condition exists causing t...

Страница 18: ...18 GRAY BLACK Wiring Diagram CORRECT WRONG Insure the wires are connected to the bottom two prongs of the hopper switch as shown...

Страница 19: ...40 Lock Nut 2 16 25480MB Access Panel 1 17 80461 Power Supply Cord 1 18 80462 Receptacle 3 Prong 1 19 891164 Auger Housing Weldment 1 20 891141 Auger 1 21 891189 Top Bushing Plate 1 22 891132 Bushing...

Страница 20: ...20 11 3 2 1 5 6 4 7 9 8 10 12 Parts Diagram 47 46 48 49...

Страница 21: ...07 Date _____________________ Engineer Name ________________________________ License No ____________________________________ Company _____________________________________ Telephone No _______________...

Страница 22: ...s pi ces d tach es Gardez ce manuel dans un lieu s r pour toute consultation ult rieure Lorsque vous nous crivez donnez toujours le num ro de mod le complet qui se trouve sur la plaque signal tique fi...

Страница 23: ...____________________________ Service de 07 Date _____________________ Nom de l ing nieur ____________________________ N de licence _________________________________ Compagnie _________________________...

Страница 24: ...2 15 83542 4 40 crou 2 16 25480MB Panneau D acc s 1 17 80461 Cordon D alimentation 1 18 80462 R ceptacle 3 Prong 1 19 891164 Auger Logement Weldment 1 20 891141 Vrille 1 21 891189 Top Bushing Plate 1...

Страница 25: ...20 Sch ma des pi ces 11 3 2 1 5 6 4 7 9 8 10 12 47 46 48 49...

Страница 26: ...SOSTAT MARRON MARRON NOIR BLANC ROUGE BLEU ORANGE PRISE MOLEX AU CIRCUIT IMPRIM PCB PRINCIPAL NOIR NOIR NOIR BLANC BLANC SOUFFLANTE DE DISTRIBUTION VENTILATEUR D VACUATION THERMISTOR Sch ma de c blage...

Страница 27: ...Cela indique que le po le fonctionne normalement et qu une condition de temp rature excessive existe provoquant l arr t du combustible Indicateur de r glage du niveau de chaleur Heat Range clignotant...

Страница 28: ...e V rifiez que le raccordement du pressostat au foyer ne contienne aucune cendre ni obstruction Le syst me vis sans fin est bloqu ou il y a une vo te de combustible dans la tr mie qui emp che le combu...

Страница 29: ...le et d paisseur correctes doivent tre utilis es NE substituez PAS le verre avec des mat riaux alternatifs Contactez votre revendeur autoris pour obtenir ce verre R installez le nouveau verre en le fi...

Страница 30: ...fi peut effectuer ces travaux Il est aussi recommand qu avant chaque saison de chauffage le syst me complet soit inspect nettoy et si n cessaire r par par un professionnel Pour nettoyer la chemin e d...

Страница 31: ...sur le bouton OFF arr t et ensuite de nouveau sur le bouton ON marche pour commencer une nouvelle s quence de mise en route 2 Si le po le a refroidi il se r initialisera l tat OFF arr t ce moment l vo...

Страница 32: ...de l eau sal e 11 Bois non s ch ou 12 Produits du papier carton contreplaqu ou panneau de particules L interdiction de br lage de ces mat riaux n interdit pas l utilisation d allume feu compos s de pa...

Страница 33: ...fin se met en marche plein r gime Si le fusible de la vis sans fin n a pas saut et que le circuit de d tection fusible fonctionne le voyant DEL Heat Range du degr de chaleur sera allum et les trois au...

Страница 34: ...justez le r glage du ventilateur de tirage essayez seulement 1 r glage au dessus ou en dessous du r glage de chaleur Il est pr f rable de laisser le po le en mode automatique VENTILATEUR DE LA PI CE L...

Страница 35: ...rage forc e est n cessaire au processus de combustion l int rieur de votre po le il est extr mement important que le syst me d vacuation soit install correctement et maintenu Et que lors du fonctionne...

Страница 36: ...ionn de la plage de chaleur d sir e 1 5 et le r glage de la plage de chaleur minimale de 1 Le T Stat n allumera ni ne teindra le po le Lorsque la temp rature ambiante souhait e est atteinte et que le...

Страница 37: ...s parois et du plafond toit de la maison mobile doit tre maintenue Un d tecteur de fum e fonctionnel doit tre install dans la m me pi ce que ce produit Il doit tre install au moins 15 pieds 4 57 m de...

Страница 38: ...rd en T de regard devra tre plac sur le tuyau avec une sortie 90 degr s hors de la maison ce point une partie de tuyau de 3 pieds 0 91m minimum devra tre ajout e avec un couvercle horizontal qui devra...

Страница 39: ...e doit tre scell en utilisant un produit vulcanis RTV pour temp ratures lev es Utilisez une ventilation de 4 pouces si la hauteur de ventilation est sup rieure 12 pieds ou si l installation se trouve...

Страница 40: ...re minimum plus grand afin d obtenir un acc s commode au panneau de contr le FIGURE 3 D GAGEMENTS DE LA PAROI LAT RALE INSTALLATION EN PARALL LE FIGURE 4 D GAGEMENTS DE LA PAROI LAT RALE INSTALLATION...

Страница 41: ...cialiste certifi NFI NE CONNECTEZ PAS CETTE UNIT UN CONDUIT OU CIRCUIT DE DISTRIBUTION D AIR INSTALLATION INCORRECTE Le fabricant ne sera pas tenu responsable des dommages caus s par un dysfonctionnem...

Страница 42: ...ar pied cube diam tre de 1 4 5 16 po longueur non sup rieure 1 5 moins de 8 200 BTU lb humidit inf rieure 8 en poids cendres inf rieure 1 en poids et sel inf rieur 300 parties par million Les granul s...

Страница 43: ...d entretien ou de nettoyage Les cendres doivent tre jet es dans un conteneur m tallique avec un couvercle d ajustement serr Le conteneur ferm dans lequel se trouvent les cendres devra tre plac sur un...

Страница 44: ...d un permis de construire Cet appareil n est pas destin tre utilis en tant que principale source de chaleur U S Environmental Protection Agency Certifi aux normes d missions de 2015 particules United...

Отзывы: