Page 21 

Protherm 50 P68.230 

Comparator 1..4 

 
PT50 provides 4 independent, versatile comparators, which integrate the functionality of a limit compar-
ator and a window comparator with adjustable tolerance time. 
 
Both  compare  variables  may  be  picked  from  a  general  variable  table.  The  comparator  mode  (“lim-
it/window”)  specifies,  whether  the  comparator  performs  a  simple  limit  compare  (“value  1  is  less 
than/greater than value2”) or a window compare (“value 1 is within/outside value 2 +- tolerance band”) 
The diagrams below show the details: 
 

 

 
Limit mode 
 
At the moment when value 1 climbs above value 2, the tolerance timer starts. If the limit violation per-
sists  during  the  entire  tolerance  time,  the  internal  limit  flag  is  raised.  If,  during  the  tolerance  time,  the 
value 1 falls below value 2, the tolerance timer is reset and a new limit violation has again to exist for 
the whole tolerance time in order to raise the limit flag. 
 
Window mode 
 
Around the value 2, there is a symmetrical tolerance window, which is twice the tolerance band wide. 
At  the  moment  when  value  1  leaves  this  tolerance  window,  the  tolerance  timer  starts  and  if  value  1 
stays outside the window  for the  entire tolerance time, the  limit flag  is raised. If  value 1  returns  to the 
tolerance window within the tolerance time, the timer is reset, a new violation must again exist for the 
whole tolerance time to raise the limit flag. 
 
If the tolerance time is set to zero, any limit violation raises the limit flag immediately. 
 
The limit flag may be used to activate a relays directly or it may be assigned to the alarm or alert sys-
tem. 
 
In the table of comparable values, there is an entry called „fixed lim”. This refers to a variable, that may 
be set to a fixed value by the user. If “fixed lim” is selected as on of the compare values, a classical limit 
compare function with a fixed compare limit results. 
 
A  good  example  for  the  use  of  the  window  comparator  mode  is  a  regulator  band  alarm  with  delayed 
action.  Set  the  comparator  mode  to  “window”,  select  the  real  value  of  a  regulator  as  value  1  and  the 
setpoint of that regulator as value 2. Then set the tolerance band and the tolerance time to the desired 
settings, assign the limit flag to the alarm system and you will have a comparator function, that raises an 
alarm if the real value stays outside the tolerance band for longer than the tolerance time. 
 
The tolerance band is expressed in the units of the compared variables. 
 

Содержание PROTHERM 50

Страница 1: ...PROT HERM 50 PROTHERM 50 Operating Manual...

Страница 2: ...tus 20 Warning and Alarm Configuration 20 Ext Analog Inputs 20 Analog Outputs 1 4 20 Comparator 1 4 21 Access control 22 Options 22 O2 actual values 23 Offsets 23 Connection diagram 24 Option PROFIBUS...

Страница 3: ...m a foil value Integrated purging automatic for O2 probe Versatile limit functions with classification in warning or alarm messages Warnings will be de leted with disappearance of the cause automatica...

Страница 4: ...necessary Since the situation is different in each case a solution was developed where an allocation of every limit or status message to a summary warning or a summery alarm A relay can be assigned in...

Страница 5: ...50 realizes only every measurement range as 0 100 and scales this in accordance with the parameterization to physical values e g 0 100 correspond to 0 40 CO Digital Inputs No digital input assigned In...

Страница 6: ...s and some few values used frequently can be adjusted additionally 3 The configuration level Additionally to the values of the setpoint level all configuration data and parameters as well as the passw...

Страница 7: ...rocess values CO and H2 normal Foil Input of a foil value with automatic calculation of the KF normal Correction Input of the correction factors and Offsets normal CAN Bus Configuration of the CAN Int...

Страница 8: ...hich is started by a process leading system Purging the probe makes only sense with carburizing processes During a probe purging the calculation of the actual value as well as the setpoint of the atmo...

Страница 9: ...direction active on or active off is selectable Two absolute limits are available whose switching points can be set to a fixed value of the control vari able The appropriate relays switch with exceedi...

Страница 10: ...ults from the setpoint relative limit Example Control variable Cp setpoint 1 00 RL1 0 05 The limit becomes active if the actual value of Cp exceeds 1 05 WA Rg1Relay Rg2Relay effective direction of a r...

Страница 11: ...djustment pulses for a servomotor the regulator takes the integral behavior of the actuator into account Cact changeover actua tor This setting is used if a proportionally valve or a mass flow control...

Страница 12: ...ow end of the working area 4 start the identification and wait for the results After the end of the process the regulator calculates the matching parameters switches itself on and approaches the setpo...

Страница 13: ...yristor controller only heating no cooling 0 magnetic valve heating and cooling 100 Servomotor gas heating 100 To avoid undershooting with negative setpoint steps Ymin may be set to values in the rang...

Страница 14: ...absolute limit 2 actively ON IDENT The IDENT function facilitates an automatic optimization of the settings of the controller Requirements for the TMP controller 1 The furnace temperature is minimum...

Страница 15: ...Selection of TCS TCUS Filter time constant of the US input in sec TCTCS Filter time constant of the TCS input in sec ThEL TC1 Selection of the thermocouple type for TC1 available are PtRh10s S PtRh13...

Страница 16: ...by ready When the foil is extracted during a foil measurement out of the furnace the PT 50 must be informed by setting this line to foil ready The PT50 remembers the corresponding Cp value in order to...

Страница 17: ...ressure are inde pendent from each other If all three O2 oOffsets are not 0 is not guaranteed that the representation forms are consistent among each other K1 K2 The calculation of the C potential wit...

Страница 18: ...Node start commands In operating mode Standalone the connection between PT50 and the I O modules are watched by nodeguarding WA Further information about the operation of the PT50 with CAN Bus Interfa...

Страница 19: ...4 wire mode The selection is done by software The MODBUS driver supports only the RTU Mode and requires a sign length of 8 bits Further information to the operation of the PT50 with MODBUS Interface...

Страница 20: ...ro cess parameters will be adopted only in Remote mode faults are transferred as external diagnostics Attention Because Input and output data are transferred constantly with profibus the master must a...

Страница 21: ...range from 0 to 100 These are the raw values of the optional CANopen moduls before the scaling to a physical measurement value Analog Outputs 1 4 PT50 provides four drivers for external analog outputs...

Страница 22: ...imer starts and if value 1 stays outside the window for the entire tolerance time the limit flag is raised If value 1 returns to the tolerance window within the tolerance time the timer is reset a new...

Страница 23: ...access with the password Options In this menu all settings which do not belong to other menus are summarized Operating mode Selection the operating mode Local Remote sees above DIGIN REMLOC Allocation...

Страница 24: ...the O2 partial pressure in percent and the LogO2 in big letters Offsets If PT50 uses for the O2 measurements it is inexpedient to use the menu correction because this shows insignificant correction v...

Страница 25: ...t verwendet wird dann m ssen Klemme 8 und 9 mit einer Br cke verbunden werden If Uth2 is not used short terminal 8 and 9 to prevent false thermocouple alarm 1 IntRL4 PE 4 THC2 TC2 NiCrNi K Sensor EMK...

Страница 26: ...d plugs Siemens 6GK1500 0EA02 Recommended cables cable type A according IEC61158 Siemens 6XV1830 0EH10 At both ends of the bus cable and only there a termination resistor must be applied Application o...

Страница 27: ...Cables with single shield for example Belden 9841 4 wire drove the receive direction uses the pins 3 and 8 the transmit direction the pins 1 and 2 Cables with single shield for example Belden 9842 Bu...

Страница 28: ...t 2 indus trial area EN 50082 2 electromagnetic compatibility basic norm distribution firmness Part 2 industrial area The conformity with the upper mentioned requests is proved by the CE sign placed o...

Отзывы: