UNITED PROCESS CONTROLS GMBH
Page 10
Protherm 50 P68.230
O2%
100% O2S
O2ppm
100PPM O2S
LogO2
-20.0
KN
1.0
TP
100°C
Actuator
Selection of the actuator for the regulator.
actuator
type of control
Continuous
The regulator switches no actuator relay. The analog output is used for an
actuator
Magnetic-valve
The actuator relay correspondents to the control values. The ON/OFF relation
correspond to the Y-value:
Y = 30% >> the UP-relay is switched on 30% of the cycle.
Y = -60% >> the DOWN-Relay is switched on 60% of the cycle.
Servomotor
The actuator relay generates adjustment pulses for a servomotor, the regulator
takes the integral behavior of the actuator into account.
Cact
, changeover actua-
tor,
This setting is used if a proportionally-valve or a mass-flow-controller acts as
actuator. The actuator relays switch the release-valves for gas (UP-Relay) as
well as air (DOWN-Relay), the proportionally-valve or the mass-flow-controller
is controller from the analog output.
Controller ON/OFF
Operating state of the controller.
DigIn LocSP
Allocation of a digital input for the selection of the local setpoint.
DigIn RefAir
Allocation of a digital input for the supervision of the reference-air of the O2-probe (WA).
If a digital input is assigned to this function, so the Atm-controller will stop if this signal is missed.