UNITED PROCESS CONTROLS GMBH
Page 14
Protherm 50 P68.230
The inputs for TC1 and TC2 can become parameterized for the linearization and compensation of dif-
ferent thermo-couple-types.
U.S.
Display of the Sensor – e.m.f. in mV
UTH1
Display of the thermo voltage of the TC1 input in mV
TC1
Display of TC1 in °C
UTH2
Display of the thermo voltage of the TC2 input in mV
TC2
Display of TC2 in °C
TCS
Display of TCS in °C. This is the value which is used for the calculation of the actual value (e.g. Cp,
O2,..)
TCS = TC1/TC2
Selection of TCS.
TCUS
Filter-time-constant of the US-input in sec.
TCTCS
Filter-time-constant of the TCS-input in sec.
ThEL TC1
Selection of the thermocouple type for TC1.
available are: PtRh10s (S), PtRh13 (R) and, Pt13Rh6(B).
TCT2
Filter-time-constant of the TC2-Eingangs in sec.
THEL TC2
Selection of the thermocouple type for TC2.
available are: PtRh10 (S), PtRh13 (R), Pt13Rh6(B), NiCrNi (K), NiCrSi (N), FeCo (J),
Prozess Values
Parameter
Meaning
CO [%]
CO value which is used for the calculation of the process values
AnaIn CO
To take the CO-value of an analyzer a ext. analog input can be used. In this case the
scaling must be set in the next two columns. With AnaIn CO = ---- the CO has to be
set manually or by a process leading system.