RECOMMENDED PRACTICES AND WARNINGS 
United Electric Controls Company recommends careful consideration 
of  the following factors when specifying and installing UE pressure and 
temperature units. Before installing a unit, the Installation and Maintenance 
instructions provided with unit must be read and understood. 

•  To avoid damaging unit, proof  pressure and maximum temperature limits 

stated in literature and on nameplates must never be exceeded, even by 
surges in the system. Operation of  the unit up to maximum pressure or 
temperature is acceptable on a limited basis (e.g., start-up, testing) but 
continuous operation must be restricted to the designated adjustable range. 
Excessive cycling at maximum pressure or temperature limits could reduce 
sensor life.

•  A back-up unit is necessary for applications where damage to a primary 

unit could endanger life, limb or property. A high or low limit switch is 
necessary for applications where a dangerous runaway condition could 
result.

•  The adjustable range must be selected so that incorrect, inadvertent or 

malicious setting at any range point cannot result in an unsafe system 
condition.  

•  Install unit where shock, vibration and ambient temperature fluctuations 

will not damage unit or affect operation. When applicable, orient unit so 
that moisture does not enter the enclosure via the electrical connection. 
When appropriate, this entry point should be sealed to prevent moisture 
entry.

•  Unit must not be altered or modified after shipment. Consult UE if  modi-

fication is necessary.  

•  Monitor operation to observe warning signs of  possible damage to unit, 

such as drift in setpoint or faulty display.  Check unit immediately.

•  Preventative maintenance and periodic testing is necessary for critical 

applications where damage could endanger property or personnel.

•  Electrical ratings stated in literature and on nameplate must not be 

exceeded. Overload on a switch can cause damage, even on the first cycle.  
Wire unit according to local and national electrical codes, using wire size 
recommended in installation sheet.

•  Do not mount unit in ambient temp. exceeding published limits.

LIMITED WARRANTY

Seller warrants that the product hereby purchased is, upon delivery, free from 
defects in material and workmanship and that any such product which is found 
to be defective in such workmanship or material will be repaired or replaced 
by Seller (Ex-works, Factory, Watertown, Massachusetts. INCOTERMS); provided, 
however, that this warranty applies only to equipment found to be so defec-
tive within a period of  24 months from the date of  manufacture by the Seller 
(36 months for the Excela, Spectra 12 and One Series products; 18 months 
for Temperature Sensors). Seller shall not be obligated under this warranty for 
alleged defects which examination discloses are due to tampering, misuse, 
neglect, improper storage, and in any case where products are disassembled 
by anyone other than authorized Seller’s representatives. EXCEPT FOR THE 
LIMITED WARRANTY OF REPAIR AND REPLACEMENT STATED ABOVE, SELLER 
DISCLAIMS ALL WARRANTIES WHATSOEVER WITH RESPECT TO THE PRODUCT, 
INCLUDING ALL IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR 
ANY PARTICULAR PURPOSE. 

LIMITATION OF SELLER’S LIABILITY

Seller’s liability to Buyer for any loss or claim, including liability incurred in 
connection with (i) breach of  any warranty whatsoever, expressed or implied, 
(ii) a breach of  contract, (iii) a negligent act or acts (or negligent failure to act) 
committed by Seller, or (iv) an act for which strict liability will be inputted to 
seller, is limited to the “limited warranty” of  repair and/or replacement as so 
stated in our warranty of  product.  In no event shall the Seller be liable for 
any special, indirect, consequential or other damages of  a like general nature, 
including, without limitation, loss of  profits or production, or loss or expenses 
of  any nature incurred by the buyer or any third party.
UE specifications subject to change without notice.

Содержание Excela 1GSWLL

Страница 1: ... TO PREVENT MOISTURE FROM ENTERING ENCLOSURE DO NOT MOUNT UNIT IN AMBIENT TEMPERATURES EXCEEDING PUBLISHED LIMITS FOR DIFFERENTIAL PRESSURE MODELS ESPECIALLY LOW RANGE UNITS MOUNT THE SENSOR LEVEL TO MINI MIZE ANY PRESSURE READING OFFSETS THE OFFSET COMMAND MAY BE USED TO ZERO THE DISPLAY SEE PAGE 5 FOR ADDITIONAL INFORMATION Excela is rated for both indoor and outdoor operation IP66 and Nema 4X w...

Страница 2: ...power supply use the test resistor supplied 1 8K Ω with the unit Loosen the four 4 Phillips head screws holding the faceplate to the enclosure Gently remove the faceplate module Dis connect the 8 wire connector from the faceplate to allow easy wiring Pass the wires through the conduit connector and connect to the terminal block You can wire the unit as a Normally Open or a Normally Closed switch T...

Страница 3: ...ax process values and the number of switch trips The dis play will revert back to the Process Display mode after scrolling Note While scrolling you can clear the values by pushing the right g arrow Pushing the right g button once the display will scroll setpoint Rise and Fall The display will revert back to the Process Display mode after scrolling ALARM CONDITION When the process goes beyond the R...

Страница 4: ...when switch trips PASSWRD Add your own 4 digit password for security OFST Allows low range value offset by 10 SPAN Change the high end by 10 LCH1 Latch switch output on rise needs to be reset manually PLUG PORT Monitors pressure fluctuations in process 1 min 1 hr 24 hr FILTER Smoothens transient pressure spikes Programmable from 1 4 to 2 seconds TRIP DELAY Like a switch timer delay trip up to 999 ...

Страница 5: ...mit Span 400 404 x 450 446 rounded LATCH MODE Similar to Manual Reset on mechanical switch The switch output can be configured to latch when the setpoint is reached on rising set point only Set Latching Mode In the Programming Mode set LCH1 to ON When the set point is crossed on increasing process parameter the switch will latch and will remain in the latched state until it is manually reset by th...

Страница 6: ...easure the voltage drop across the switch connected to the terminal block A properly functioning Excela electronic switch will exhibit the following voltage levels Model Voltage when switch is open Voltage when switch is closed 1GSWLL 8 50 VDC 5 VDC DISPLAY MODULE CALIBRATION The Serial on the module and the enclosure must match for proper operation Swapping modules among similar ranges would resu...

Страница 7: ...d clear the error and operate normally If error continues check for sensor damage due to over range exposure Overrange Process input is above 103 of range PRESSURE and TEMPERATURE above range value Automatic Reset when process variable returns to normal Underrange Process input is be low 1 25 of range PRESSURE and TEMPERATURE below range value Automatic Reset when process variable returns to norma...

Страница 8: ...RD CONFIRM PWORD PWORD CONFIRMED IF ON SET BLINKING DIGIT IF OFF DISCARD NEW PWORD POS NEG 8888 POS NEG ON OFF 8888 Both FILTER NOTE while scrolling pressing the right arrow will clear MAX MIN TRIPS values Advanced Menu OFF 1 4S 1 2S 1Sec 2Sec OFF and 1 4 Sec settings not available on temperature models TRIP DELAY ON OFF 8888 ON OFF SAVE CHNG NOTE Ifentriesareoutofrange ERR messagewillflashonscree...

Страница 9: ...IM_1GSW 02 www ueonline com 9 DIMENSIONAL DRAWINGS Model 1GSWLL Gauge Pressure Sensor Model 1GSWLL Differential Pressure Sensor ...

Страница 10: ...IM_1GSW 02 www ueonline com 10 Model 1GSWLL Temperature Model R Sensor Model 1GSWLL Temperature Model L Sensor ...

Страница 11: ...ight arrow button and continue to record new min max values 4 Press the right key to display the switch setpoints Verify that the setpoints are correct 5 To confirm process display on Excela connect calibration gauge to the Excela and verify that both displays match within tolerance If minor adjustment is needed up to 10 of range use the offset and span features within Excela s advanced programmin...

Страница 12: ...be used to zero the display see page xx for additional information Pour les modèles de pression différentielle de pressions faibles montez le niveau du capteur afin de minimiser tout décalage de lecture de pression La commande décalée peut être utilisée pour mettre l affichage à zéro voir la page xx pour plus d informations 1 Never insert any object into the pressure sensor opening Damage to the s...

Страница 13: ...sonnel Electrical ratings stated in literature and on nameplate must not be exceeded Overload on a switch can cause damage even on the first cycle Wire unit according to local and national electrical codes using wire size recommended in installation sheet Do not mount unit in ambient temp exceeding published limits LIMITED WARRANTY Seller warrants that the product hereby purchased is upon delivery...

Отзывы: