Recommended Maintenance Procedures

Excela is an electronic switch with a digital display.  It has internal diagnostics that continuously check its 
electronics to make sure it is operational and alarms if  it detects an error.

UEC recommends the following annual checks on the Excela product line to keep the unit in optimal operat-
ing form for the intended function.  

1.  Check unit for any visible damage, corrosion, leakage or contamination. Clean and repair as 

needed.

2.  For electrical testing, bypass the PLC connection to avoid false trips.  For test, use a 24 VDC 

power source and a 1.8K ohm resistor on the COM terminal.

3.  Press the up/down arrow button to view the maximum and minimum process parameters that 

have been recorded by the unit.  To clear values, press the right arrow button and continue to 
record new min/max values. 

4.  Press the right key to display the switch setpoints.  Verify that the setpoints are correct.
5.  To confirm process display on Excela, connect calibration gauge to the Excela and verify that both 

displays match, within tolerance. If  minor adjustment is needed, up to +/- 10 % of  range, use the 
offset and span features within Excela’s advanced programming menu to adjust.

6.  If  the display shows error messages, check the Installation & Maintenance sheet for potential 

causes and corrective actions.

To help with the maintenance, QR codes to the various videos and documents are listed below.

Basic Programming 

Video

Advanced Programming 

Video

Wiring and 

Setup Video

The Excela is a robust and reliable instrument that requires minimum yearly maintenance.  If  you have any 
questions related to this maintenance guide, please contact United Electric Controls at insidesales@ueonline.
com or call inside sales at Tel: +1 617-923-6977 for additional information.

Содержание Excela 1GSWLL

Страница 1: ... TO PREVENT MOISTURE FROM ENTERING ENCLOSURE DO NOT MOUNT UNIT IN AMBIENT TEMPERATURES EXCEEDING PUBLISHED LIMITS FOR DIFFERENTIAL PRESSURE MODELS ESPECIALLY LOW RANGE UNITS MOUNT THE SENSOR LEVEL TO MINI MIZE ANY PRESSURE READING OFFSETS THE OFFSET COMMAND MAY BE USED TO ZERO THE DISPLAY SEE PAGE 5 FOR ADDITIONAL INFORMATION Excela is rated for both indoor and outdoor operation IP66 and Nema 4X w...

Страница 2: ...power supply use the test resistor supplied 1 8K Ω with the unit Loosen the four 4 Phillips head screws holding the faceplate to the enclosure Gently remove the faceplate module Dis connect the 8 wire connector from the faceplate to allow easy wiring Pass the wires through the conduit connector and connect to the terminal block You can wire the unit as a Normally Open or a Normally Closed switch T...

Страница 3: ...ax process values and the number of switch trips The dis play will revert back to the Process Display mode after scrolling Note While scrolling you can clear the values by pushing the right g arrow Pushing the right g button once the display will scroll setpoint Rise and Fall The display will revert back to the Process Display mode after scrolling ALARM CONDITION When the process goes beyond the R...

Страница 4: ...when switch trips PASSWRD Add your own 4 digit password for security OFST Allows low range value offset by 10 SPAN Change the high end by 10 LCH1 Latch switch output on rise needs to be reset manually PLUG PORT Monitors pressure fluctuations in process 1 min 1 hr 24 hr FILTER Smoothens transient pressure spikes Programmable from 1 4 to 2 seconds TRIP DELAY Like a switch timer delay trip up to 999 ...

Страница 5: ...mit Span 400 404 x 450 446 rounded LATCH MODE Similar to Manual Reset on mechanical switch The switch output can be configured to latch when the setpoint is reached on rising set point only Set Latching Mode In the Programming Mode set LCH1 to ON When the set point is crossed on increasing process parameter the switch will latch and will remain in the latched state until it is manually reset by th...

Страница 6: ...easure the voltage drop across the switch connected to the terminal block A properly functioning Excela electronic switch will exhibit the following voltage levels Model Voltage when switch is open Voltage when switch is closed 1GSWLL 8 50 VDC 5 VDC DISPLAY MODULE CALIBRATION The Serial on the module and the enclosure must match for proper operation Swapping modules among similar ranges would resu...

Страница 7: ...d clear the error and operate normally If error continues check for sensor damage due to over range exposure Overrange Process input is above 103 of range PRESSURE and TEMPERATURE above range value Automatic Reset when process variable returns to normal Underrange Process input is be low 1 25 of range PRESSURE and TEMPERATURE below range value Automatic Reset when process variable returns to norma...

Страница 8: ...RD CONFIRM PWORD PWORD CONFIRMED IF ON SET BLINKING DIGIT IF OFF DISCARD NEW PWORD POS NEG 8888 POS NEG ON OFF 8888 Both FILTER NOTE while scrolling pressing the right arrow will clear MAX MIN TRIPS values Advanced Menu OFF 1 4S 1 2S 1Sec 2Sec OFF and 1 4 Sec settings not available on temperature models TRIP DELAY ON OFF 8888 ON OFF SAVE CHNG NOTE Ifentriesareoutofrange ERR messagewillflashonscree...

Страница 9: ...IM_1GSW 02 www ueonline com 9 DIMENSIONAL DRAWINGS Model 1GSWLL Gauge Pressure Sensor Model 1GSWLL Differential Pressure Sensor ...

Страница 10: ...IM_1GSW 02 www ueonline com 10 Model 1GSWLL Temperature Model R Sensor Model 1GSWLL Temperature Model L Sensor ...

Страница 11: ...ight arrow button and continue to record new min max values 4 Press the right key to display the switch setpoints Verify that the setpoints are correct 5 To confirm process display on Excela connect calibration gauge to the Excela and verify that both displays match within tolerance If minor adjustment is needed up to 10 of range use the offset and span features within Excela s advanced programmin...

Страница 12: ...be used to zero the display see page xx for additional information Pour les modèles de pression différentielle de pressions faibles montez le niveau du capteur afin de minimiser tout décalage de lecture de pression La commande décalée peut être utilisée pour mettre l affichage à zéro voir la page xx pour plus d informations 1 Never insert any object into the pressure sensor opening Damage to the s...

Страница 13: ...sonnel Electrical ratings stated in literature and on nameplate must not be exceeded Overload on a switch can cause damage even on the first cycle Wire unit according to local and national electrical codes using wire size recommended in installation sheet Do not mount unit in ambient temp exceeding published limits LIMITED WARRANTY Seller warrants that the product hereby purchased is upon delivery...

Отзывы: