background image

IM_1GSW-02

www.ueonline.com

5

OFFSET:

  

Offset adjustment changes the zero point without changing the slope of the calibration line.  The Excela is factory calibrated to 

0.5% of sensor range at room temperature. In some applications, it may be necessary to re-calibrate the unit in the field. Offset 

allows the user to enter a positive (“POS”) or negative (“NEG”) offset to the display readings. An offset of up to +/- 10% of the 

range is allowed.

NOTE: 

Any numerical value entered other than 0.00 will cause the display to indicate “Offset” just above the process reading in 

the process display.

USE OF THIS OPTION MAY CREATE A CONDITION WHERE THE DISPLAY MAY INDICATE “0.00” WHEN SIGNIFICANT PRES-

SURE OR TEMPERATURE(10% OF RANGE) EXISTS IN THE SYSTEM. INDEPENDENT VERIFICATION OF THE PROCESS VARIABLE 

SHOULD BE DONE PRIOR TO MAINTENANCE ON THE SYSTEM IF “OFFSET” APPEARS ON THE PROCESS DISPLAY.

SPAN: 

SPAN adjustment adjusts the high end of the range by ± 10% by changing the slope of the line while holding the zero point 

fixed.

To calculate the SPAN value, apply a reference source below full scale to the Excela sensor. Record the value that shows on the 

Excela display and the reference source value. Divide the reference source value by the display value and then multiply the 

result by the sensor’s upper range value.

FORMULA: SPAN = reference source / display value x upper range value

•  Pressure example: For a sensor range of 0 - 100 psi, choose a reference source (90) below the upper range limit (100) to 

prevent an over range condition. Divide the reference source value from the resulting display value (88). Multiply the result 

by the upper range limit. Span = 90 / 88 x 100 = 102 (rounded)

•  Temperature example: For a sensor range of -40 to 450ºF, choose a reference source (400) below the upper range limit 

(450) to prevent an over range condition. Divide the reference source value from the resulting display value (404). Multiply 

the result by the upper range limit. Span = 400 / 404 x 450 = 446 (rounded)

LATCH MODE:

(Similar to Manual Reset on mechanical switch)

The switch output can be configured to latch when the setpoint is reached on rising set-point only.

•  Set Latching Mode: In the Programming Mode, set “LCH1” to “ON”.  When the set-point is crossed on increasing process 

parameter, the switch will latch, and will remain in the latched state until it is manually reset by the user.

•  To clear a Latched Output: First hit both buttons simultaneously, then “MAN RSET” will appear on the screen. To clear and 

exit, press both buttons 

og

PLUGGED PORT:

The Excela has the ability to monitor the sensor for changes over time, and can indicate that the process port has become 

blocked, or plugged. The time and the pressure fluctuation is adjustable to match the application.

There are four possible settings for the detection time: 

OFF 

• 1 Min.  • 1 Hr.  • 24 Hrs.

When the feature is enabled, the user must then enter the plugged port range. The number is limited to +/- 10% of the full-

scale sensor range.

If the pressure does not vary more than the threshold value during the selected time, the unit goes into alarm mode. 

Filter:

In some applications, it is desirable to “dampen” the switch response and prevent intermittent false trips due to pressure 

spikes or other transient/isolated events. The Filter feature provides a software digital filter with a programmable time constant 

for suppressing certain transient short-duration events. 

Selection for pressure models: 

 

OFF 

• 1/4 Sec. 

• 1/2 Sec. 

• 1 Sec.   

• 2 Sec.

Selection for temperature models: 

 

 

 

• 1/2 Sec. 

• 1 Sec.   

• 2 Sec.

DELAY:

The Trip Delay provides a configurable delay for switch trips with a range of up to 999.9 seconds. 

To program the delay turn the feature on and then set the number of seconds for the delay.

If latch mode is activated, the Red LED will continue to flash even if the value drops below the Fall setting. Refer to Latch func-

tion on page 5 to clear a latched output.

NOTE: 

Enabling the trip delay function would delay notification of a tripped process event. Select an appropriate time delay 

that will still accommodate for sufficient response time to a tripped event.

Содержание Excela 1GSWLL

Страница 1: ... TO PREVENT MOISTURE FROM ENTERING ENCLOSURE DO NOT MOUNT UNIT IN AMBIENT TEMPERATURES EXCEEDING PUBLISHED LIMITS FOR DIFFERENTIAL PRESSURE MODELS ESPECIALLY LOW RANGE UNITS MOUNT THE SENSOR LEVEL TO MINI MIZE ANY PRESSURE READING OFFSETS THE OFFSET COMMAND MAY BE USED TO ZERO THE DISPLAY SEE PAGE 5 FOR ADDITIONAL INFORMATION Excela is rated for both indoor and outdoor operation IP66 and Nema 4X w...

Страница 2: ...power supply use the test resistor supplied 1 8K Ω with the unit Loosen the four 4 Phillips head screws holding the faceplate to the enclosure Gently remove the faceplate module Dis connect the 8 wire connector from the faceplate to allow easy wiring Pass the wires through the conduit connector and connect to the terminal block You can wire the unit as a Normally Open or a Normally Closed switch T...

Страница 3: ...ax process values and the number of switch trips The dis play will revert back to the Process Display mode after scrolling Note While scrolling you can clear the values by pushing the right g arrow Pushing the right g button once the display will scroll setpoint Rise and Fall The display will revert back to the Process Display mode after scrolling ALARM CONDITION When the process goes beyond the R...

Страница 4: ...when switch trips PASSWRD Add your own 4 digit password for security OFST Allows low range value offset by 10 SPAN Change the high end by 10 LCH1 Latch switch output on rise needs to be reset manually PLUG PORT Monitors pressure fluctuations in process 1 min 1 hr 24 hr FILTER Smoothens transient pressure spikes Programmable from 1 4 to 2 seconds TRIP DELAY Like a switch timer delay trip up to 999 ...

Страница 5: ...mit Span 400 404 x 450 446 rounded LATCH MODE Similar to Manual Reset on mechanical switch The switch output can be configured to latch when the setpoint is reached on rising set point only Set Latching Mode In the Programming Mode set LCH1 to ON When the set point is crossed on increasing process parameter the switch will latch and will remain in the latched state until it is manually reset by th...

Страница 6: ...easure the voltage drop across the switch connected to the terminal block A properly functioning Excela electronic switch will exhibit the following voltage levels Model Voltage when switch is open Voltage when switch is closed 1GSWLL 8 50 VDC 5 VDC DISPLAY MODULE CALIBRATION The Serial on the module and the enclosure must match for proper operation Swapping modules among similar ranges would resu...

Страница 7: ...d clear the error and operate normally If error continues check for sensor damage due to over range exposure Overrange Process input is above 103 of range PRESSURE and TEMPERATURE above range value Automatic Reset when process variable returns to normal Underrange Process input is be low 1 25 of range PRESSURE and TEMPERATURE below range value Automatic Reset when process variable returns to norma...

Страница 8: ...RD CONFIRM PWORD PWORD CONFIRMED IF ON SET BLINKING DIGIT IF OFF DISCARD NEW PWORD POS NEG 8888 POS NEG ON OFF 8888 Both FILTER NOTE while scrolling pressing the right arrow will clear MAX MIN TRIPS values Advanced Menu OFF 1 4S 1 2S 1Sec 2Sec OFF and 1 4 Sec settings not available on temperature models TRIP DELAY ON OFF 8888 ON OFF SAVE CHNG NOTE Ifentriesareoutofrange ERR messagewillflashonscree...

Страница 9: ...IM_1GSW 02 www ueonline com 9 DIMENSIONAL DRAWINGS Model 1GSWLL Gauge Pressure Sensor Model 1GSWLL Differential Pressure Sensor ...

Страница 10: ...IM_1GSW 02 www ueonline com 10 Model 1GSWLL Temperature Model R Sensor Model 1GSWLL Temperature Model L Sensor ...

Страница 11: ...ight arrow button and continue to record new min max values 4 Press the right key to display the switch setpoints Verify that the setpoints are correct 5 To confirm process display on Excela connect calibration gauge to the Excela and verify that both displays match within tolerance If minor adjustment is needed up to 10 of range use the offset and span features within Excela s advanced programmin...

Страница 12: ...be used to zero the display see page xx for additional information Pour les modèles de pression différentielle de pressions faibles montez le niveau du capteur afin de minimiser tout décalage de lecture de pression La commande décalée peut être utilisée pour mettre l affichage à zéro voir la page xx pour plus d informations 1 Never insert any object into the pressure sensor opening Damage to the s...

Страница 13: ...sonnel Electrical ratings stated in literature and on nameplate must not be exceeded Overload on a switch can cause damage even on the first cycle Wire unit according to local and national electrical codes using wire size recommended in installation sheet Do not mount unit in ambient temp exceeding published limits LIMITED WARRANTY Seller warrants that the product hereby purchased is upon delivery...

Отзывы: