EXCELA ERROR MESSAGES

The Excela diagnostics are capable of detecting many possible error conditions.  Some error conditions will clear 

automatically when the parameter returns to normal; others require the device to be powered down and restarted; 

and some may require repair or replacement.  A list of error conditions are listed below.

Possible Corrective Actions

Error  Condition 

and Code

Message

Probable Causes

Try This First

Other Options

Switch Output

Codes  E44, E45, 

E49, E50

CRC error on Se-

rial memory used to 

store calibration / 

configuration data.

Cycle Power. In most 

cases, it should clear 

the error and operate 

normally.

If error does not clear, unit 

has to be returned for factory 

repair.

Switch output indicates 

alarm conditions based on 

the wiring set-up of the unit 

and matches the Red LED 

output.

KEY STUCK

Keypad button 

shorted.

Cycle Power. In most 

cases, it should clear 

the error and operate 

normally.

If error does not clear, unit 

has to be returned for factory 

repair.

"EXTREME OVER-

RANGE 

E88"

TEMPERATURE 

device process 

input above 110% of 

range.

Cycle Power. In most 

cases, it should clear 

the error and operate 

normally.

If error continues, check for 

sensor damage due to over 

range exposure. 

"EXTREME OVER-

RANGE 

E88"

PRESSURE device 

process input above 

150% of range.

Cycle Power. In most 

cases, it should clear 

the error and operate 

normally.

If error continues, check for 

sensor damage due to over 

range exposure. 

Overrange

Process input is 

above 103% of 

range.

PRESSURE and 

TEMPERATURE above 

range value.

Automatic Reset when 

process variable returns to 

normal.

Underrange

Process input is be-

low -1.25% of range

PRESSURE and 

TEMPERATURE below 

range value.

Automatic Reset when 

process variable returns to 

normal.

PLUG

Process is not vary-

ing outside of Plug 

Port Window setting.

Is pressure / tempera-

ture dynamic? Is sen-

sor clogged? Is plug 

port setup OK?

Turn feature off. 

"Reference Fault 

E09, E13, E14"

Hardware internal 

voltages are out of 

range.

Reference Fault can 

be caused by the 

presence of electrical 

noise. Eliminate elec-

trical noise sources. 

If error does not clear, unit 

has to be returned for factory 

repair.

Watchdog Fault

The processor is 

being reset automati-

cally on an internal 

fault. Could be 

caused by transients 

on the power supply 

or unit connected 

to a load resistance 

that is too high.

Review load resis-

tance. Cycle power. In 

most cases, it should 

clear the error and 

operate normally. 

If error continues, try a differ-

ent power supply or unit has 

to be returned to factory for 

repair.

All errors that start 

with up to three 

alphanumeric 

digits

Causes are various

Cycle Power. In most 

cases, it should clear 

the error and operate 

normally.

If error does not clear, unit 

has to be returned for factory 

repair.

Note: If the error remains after power cycling, please contact UE Inside Sales at [email protected] or call 

+1 (617) 923-6977

Содержание Excela 1GSWLL

Страница 1: ... TO PREVENT MOISTURE FROM ENTERING ENCLOSURE DO NOT MOUNT UNIT IN AMBIENT TEMPERATURES EXCEEDING PUBLISHED LIMITS FOR DIFFERENTIAL PRESSURE MODELS ESPECIALLY LOW RANGE UNITS MOUNT THE SENSOR LEVEL TO MINI MIZE ANY PRESSURE READING OFFSETS THE OFFSET COMMAND MAY BE USED TO ZERO THE DISPLAY SEE PAGE 5 FOR ADDITIONAL INFORMATION Excela is rated for both indoor and outdoor operation IP66 and Nema 4X w...

Страница 2: ...power supply use the test resistor supplied 1 8K Ω with the unit Loosen the four 4 Phillips head screws holding the faceplate to the enclosure Gently remove the faceplate module Dis connect the 8 wire connector from the faceplate to allow easy wiring Pass the wires through the conduit connector and connect to the terminal block You can wire the unit as a Normally Open or a Normally Closed switch T...

Страница 3: ...ax process values and the number of switch trips The dis play will revert back to the Process Display mode after scrolling Note While scrolling you can clear the values by pushing the right g arrow Pushing the right g button once the display will scroll setpoint Rise and Fall The display will revert back to the Process Display mode after scrolling ALARM CONDITION When the process goes beyond the R...

Страница 4: ...when switch trips PASSWRD Add your own 4 digit password for security OFST Allows low range value offset by 10 SPAN Change the high end by 10 LCH1 Latch switch output on rise needs to be reset manually PLUG PORT Monitors pressure fluctuations in process 1 min 1 hr 24 hr FILTER Smoothens transient pressure spikes Programmable from 1 4 to 2 seconds TRIP DELAY Like a switch timer delay trip up to 999 ...

Страница 5: ...mit Span 400 404 x 450 446 rounded LATCH MODE Similar to Manual Reset on mechanical switch The switch output can be configured to latch when the setpoint is reached on rising set point only Set Latching Mode In the Programming Mode set LCH1 to ON When the set point is crossed on increasing process parameter the switch will latch and will remain in the latched state until it is manually reset by th...

Страница 6: ...easure the voltage drop across the switch connected to the terminal block A properly functioning Excela electronic switch will exhibit the following voltage levels Model Voltage when switch is open Voltage when switch is closed 1GSWLL 8 50 VDC 5 VDC DISPLAY MODULE CALIBRATION The Serial on the module and the enclosure must match for proper operation Swapping modules among similar ranges would resu...

Страница 7: ...d clear the error and operate normally If error continues check for sensor damage due to over range exposure Overrange Process input is above 103 of range PRESSURE and TEMPERATURE above range value Automatic Reset when process variable returns to normal Underrange Process input is be low 1 25 of range PRESSURE and TEMPERATURE below range value Automatic Reset when process variable returns to norma...

Страница 8: ...RD CONFIRM PWORD PWORD CONFIRMED IF ON SET BLINKING DIGIT IF OFF DISCARD NEW PWORD POS NEG 8888 POS NEG ON OFF 8888 Both FILTER NOTE while scrolling pressing the right arrow will clear MAX MIN TRIPS values Advanced Menu OFF 1 4S 1 2S 1Sec 2Sec OFF and 1 4 Sec settings not available on temperature models TRIP DELAY ON OFF 8888 ON OFF SAVE CHNG NOTE Ifentriesareoutofrange ERR messagewillflashonscree...

Страница 9: ...IM_1GSW 02 www ueonline com 9 DIMENSIONAL DRAWINGS Model 1GSWLL Gauge Pressure Sensor Model 1GSWLL Differential Pressure Sensor ...

Страница 10: ...IM_1GSW 02 www ueonline com 10 Model 1GSWLL Temperature Model R Sensor Model 1GSWLL Temperature Model L Sensor ...

Страница 11: ...ight arrow button and continue to record new min max values 4 Press the right key to display the switch setpoints Verify that the setpoints are correct 5 To confirm process display on Excela connect calibration gauge to the Excela and verify that both displays match within tolerance If minor adjustment is needed up to 10 of range use the offset and span features within Excela s advanced programmin...

Страница 12: ...be used to zero the display see page xx for additional information Pour les modèles de pression différentielle de pressions faibles montez le niveau du capteur afin de minimiser tout décalage de lecture de pression La commande décalée peut être utilisée pour mettre l affichage à zéro voir la page xx pour plus d informations 1 Never insert any object into the pressure sensor opening Damage to the s...

Страница 13: ...sonnel Electrical ratings stated in literature and on nameplate must not be exceeded Overload on a switch can cause damage even on the first cycle Wire unit according to local and national electrical codes using wire size recommended in installation sheet Do not mount unit in ambient temp exceeding published limits LIMITED WARRANTY Seller warrants that the product hereby purchased is upon delivery...

Отзывы: