background image

Avoid bending or coiling the capillary tube tighter
than 1/2” radius. Exercise caution when making
bends near the capillary ends. 

If a separable well or union connector is used 
follow separate instructions included with them.

DISCONNECT ALL SUPPLY CIRCUITS
BEFORE WIRING.

ELECTRICAL RATINGS STATED IN LIT-
ERATURE AND ON NAMEPLATE

SHOULD NEVER BE EXCEEDED. OVERLOAD
ON A SWITCH CAN CAUSE FAILURE ON THE
FIRST CYCLE.

WIRE UNITS ACCORDING TO LOCAL
AND NATIONAL ELECTRICAL CODES.

MAXIMUM RECOMMENDED WIRE SIZE IS 14
AWG.

Types 800, 802, 802P

(Enclosed units)
Connect the electrical conduit to the case 
securing it with the grounding locknut supplied.

Note: Unless control is connected to a metallic
conduit, grounding bushing should be removed
from grounding wire. A separate conductor should
be provided from grounding system directly to the
non-current carrying metal parts of control (splice
the grounding wire).

Conduit opening is available on the left side as
standard. It can be supplied on the right side on
request. See PART III, option M007. Wire through
the 7/8” conduit hole directly to the lead-wire(s)
provided, color coded as follows, or to the optional
terminal block.

Switch 1

Switch 2

Common

Violet

Yellow

Normally Open

Blue

Orange

Normally Closed

Black

Red

Avoid bending or coiling the capillary tube 

See wiring Diagrams Figure 2A and 2B.
Optional terminal block wiring is available for 
single or dual switch controls (option M100).
See Figure 2C.

To Surface Mount

(Explosion Proof Types)
820E and 822E type units must be surface
mounted.  Drill mounting holes per Figure 1C.

(Option M449)  
Attach 2 mounting ears found in separate 
package to recessed areas on back side of
enclosure by means of 2 self-tapping screws.
Mount to surface per Figure 1D.  On dual switch
explosion-proof types requiring seal fitting,
install the nipple and the seal fitting prior to sur-
face mounting the controller. 

Mounting Bulb and Capillary

Fully immerse the bulb and 6” of capillary in the
control zone.  For best control it is generally
desirable to place the bulb close to the heating
or cooling source in order to sense temperature
fluctuations quickly.  Be sure to locate the bulb
so it will not be exposed to temperature beyond
the instruments range limits.

Try to place the remaining capillary adjacent 
to the control head so it will sense the same
ambient temperatures (control is ambient tem-
perature compensated).

Unless otherwise specified, factory calibration,
allows  for 6” of capillary tube in the control
zone.  If longer lengths are required recalibra-
tion may be necessary. Follow the procedure
outlined in PART II. 

‘C’ style bulbs can be coiled or shaped to fit the
installation. Avoid sharp bends and coils tighter
than a 2” radius. Do not bend ‘B’ style bulbs.  

F

igure 1C  - Explosion-Proof Mounting

Figure 1D - Surface Mounting

WIRING

Clearance for 1/4

screw (4) places

Clearance for #10

screw - (2) places

Содержание 800

Страница 1: ...unting 800 or 802 type controls it may be necessary to remove adjustment knob and front cover The knob is secured with a 5 64 Allen Setscrew The cover is secured by four screws at the corners MOUNTING The controller may be mounted in any position to either a surface or panel 1 4 thick maximum Locate it where vibration shock and ambient temperature fluctuations are minimal It is recom mended that m...

Страница 2: ... 2B Optional terminal block wiring is available for single or dual switch controls option M100 See Figure 2C To Surface Mount Explosion Proof Types 820E and 822E type units must be surface mounted Drill mounting holes per Figure 1C Option M449 Attach 2 mounting ears found in separate package to recessed areas on back side of enclosure by means of 2 self tapping screws Mount to surface per Figure 1...

Страница 3: ...t together within 5 of the dial range Turning the knob positions both switch simultaneously maintain ing a constant separation between switches Replace cover and adjustment knob if removed during installation Controller is ready for operation Turn setting pointer to desired control temperature and start up the process To suit particular process conditions or for greater controller accuracy it may ...

Страница 4: ...ct test lights to indicate switch operation or listen for the individual switch clicks Note The adjustment knob slides off adjustment shaft for all controls except the 802 The 802 requires a 5 64 allen wrench Be sure to replace gasket when re assembling In Process Adjustments Use an accurate test thermometer such as a thermocouple with its probe mounted directly to the center of the sensing bulb B...

Страница 5: ...itch assembly to pivot post Part III Replacements The set point of switch 1 is determined by the red Adjustment Pointer The set point of switch 2 may be adjusted by up to 25 of the range span below the switch 1 set point by turning adjust ment D in clockwise See Figure 4 The set point of switch 2 should not be above that of switch 1 To align switch 1 to the Adjustment Pointer loosen adjustment A a...

Страница 6: ...mounting screws the switch and the insulator 3 Remove leadwires from switch and transfer to new switch 4 Install insulator with new switch and mount in control 5 Install terminal block and adjust temperature setting per PART II Dual Switch Types 1 Remove die cast aluminum cover unscrew and remove terminal block and insulator letting terminal block hang 2 Unscrew terminal block supports and remove ...

Страница 7: ...Dimensions 800 Series 820E 822E ...

Страница 8: ...s using wire size recommended in installation sheet Use only factory authorized replacement parts and procedures Do not mount unit in ambient temp exceeding published limits For remote mounted temperature units capillary lengths beyond 10 feet can increase chance of error and may require re calibration of set point and indication LIMITED WARRANTY Seller warrants that the product hereby purchased i...

Отзывы: