background image

Types 800S, 802S and 802PS

(Skeleton units)
Wire directly to the leadwires, in the same 
manner as above.

Types 820E and 822E

(Explosion-proof)
Connect the electrical conduit directly to the die-
cast aluminum enclosure via 3/4 NPTF connec-
tion. Wire directly to the terminal block. See
Figure 2D. Wiring enclosure includes grounding 
terminal.

Figure 2D - Explosion Proof

Tools Needed

5/64th” Allen Wrench

5/16” Open End Wrench (2 required)

Screwdriver

1/4” Open End Wrench

9/16” Open End Wrench

Switch Settings

(Dual switch types only)
The basic enclosed and skeleton dual switch
controllers are furnished with a choice of
individual or common adjustment of set points
as described below.

Types 802 and 802S have a separate knob and
pointer for each switch. Turn black knob for
switch #2 and turn green inserted knob for
switch #1. Set points are shown by individual
pointers and may be separated up to 100% of
dial range apart, so long as the red pointer is
set higher than the green pointer.

Types 802P, 822E AND 802PS have a single
knob and pointer for both switches. Both 
switches are standardly, factory set together
within 5% of the dial range. Turning the knob
positions both switch simultaneously, maintain-
ing a constant separation between switches.  

Replace cover and adjustment knob if removed
during installation. Controller is ready for 
operation. Turn setting pointer to desired 
control temperature and start up the process.
To suit particular process conditions or for
greater controller accuracy it may be desirable
to make slight alterations to the set point or 
indicator reading.  Procedures for making these
adjustments are described below.

Note:

Indicating Pointer Deflection: 

The indicating pointers will read slightly low
when the bulb temperature is 15° above the
controller setting. This deflection is normal and
repeatable (approximately 0.5% of scale range
on single switch models) and is due to the
transference of the switching mechanism load
to the thermal system. It can be measured by
moving the setting pointer from the high to the
low end of the scale and observing the resultant
indicating pointer deflection.

Note: Prior to making any controller  adjust-
ments, the cover and adjustment knobs should
be removed. When adjustments are completed,
all applicable parts should be replaced.

Part II - Adjustments 

Figure 2A - Dual Switch

Figure 2B - Single Switch 

Figure 2C - Terminal Block Option

Содержание 800

Страница 1: ...unting 800 or 802 type controls it may be necessary to remove adjustment knob and front cover The knob is secured with a 5 64 Allen Setscrew The cover is secured by four screws at the corners MOUNTING The controller may be mounted in any position to either a surface or panel 1 4 thick maximum Locate it where vibration shock and ambient temperature fluctuations are minimal It is recom mended that m...

Страница 2: ... 2B Optional terminal block wiring is available for single or dual switch controls option M100 See Figure 2C To Surface Mount Explosion Proof Types 820E and 822E type units must be surface mounted Drill mounting holes per Figure 1C Option M449 Attach 2 mounting ears found in separate package to recessed areas on back side of enclosure by means of 2 self tapping screws Mount to surface per Figure 1...

Страница 3: ...t together within 5 of the dial range Turning the knob positions both switch simultaneously maintain ing a constant separation between switches Replace cover and adjustment knob if removed during installation Controller is ready for operation Turn setting pointer to desired control temperature and start up the process To suit particular process conditions or for greater controller accuracy it may ...

Страница 4: ...ct test lights to indicate switch operation or listen for the individual switch clicks Note The adjustment knob slides off adjustment shaft for all controls except the 802 The 802 requires a 5 64 allen wrench Be sure to replace gasket when re assembling In Process Adjustments Use an accurate test thermometer such as a thermocouple with its probe mounted directly to the center of the sensing bulb B...

Страница 5: ...itch assembly to pivot post Part III Replacements The set point of switch 1 is determined by the red Adjustment Pointer The set point of switch 2 may be adjusted by up to 25 of the range span below the switch 1 set point by turning adjust ment D in clockwise See Figure 4 The set point of switch 2 should not be above that of switch 1 To align switch 1 to the Adjustment Pointer loosen adjustment A a...

Страница 6: ...mounting screws the switch and the insulator 3 Remove leadwires from switch and transfer to new switch 4 Install insulator with new switch and mount in control 5 Install terminal block and adjust temperature setting per PART II Dual Switch Types 1 Remove die cast aluminum cover unscrew and remove terminal block and insulator letting terminal block hang 2 Unscrew terminal block supports and remove ...

Страница 7: ...Dimensions 800 Series 820E 822E ...

Страница 8: ...s using wire size recommended in installation sheet Use only factory authorized replacement parts and procedures Do not mount unit in ambient temp exceeding published limits For remote mounted temperature units capillary lengths beyond 10 feet can increase chance of error and may require re calibration of set point and indication LIMITED WARRANTY Seller warrants that the product hereby purchased i...

Отзывы: