U01 Set-Back
Humidification
Setpoint > 45.0%
Prop Band> 05.0%
Shown above are the Set-Back screens available for change
Set Points for the Modes of operation for Set-Back control
U01
Enable Unoccupied
Control
Blower ON >Yes
Cooling >Yes
Heating >Yes
Dehumidify >Yes
Humidify >Yes
Enable each of the Modes of Operation that should operate
during the Unoccupied Control Mode The enable points
and set points follow the same principle Cooling will
automatically appear Heating will only appear if heaters
are enabled within the Factory Menu. Dehumidification will
appear when either the Return Humidity or Space Humidity
Sensor is enabled, and Humidification will only appear when
either the Return Humidity or Space Humidity is enabled
and a Humidifier is installed.
U01 Unoccupied
Cooling
Setpoint > 78.0 °F
Prop Band> 02.0 °F
U01 Unoccupied
Heating
Setpoint > 68.0 °F
Prop Band> 02.0 °F
U01 Unoccupied
Dehumidification
Setpoint > 58.0%
Prop Band> 05.0%