Installation, Operation and Maintenance Manual
Marvel Mini
33
Subject to change without notice.
120.9-IM (1218)
DANGER:
BEFORE ATTEMPTING TO TROUBLESHOOT
A SYSTEM ALARM, BE AWARE THAT REFRIGERANT
CONTAINED IN EACH COMPRESSOR SYSTEM AND
HOT WATER OR STEAM FROM HEATING COILS
CAN CAUSE SEVERE BURNS HIGH VOLTAGE AND
OPERATING FAN DRIVES ALSO PRESENT HAZARDOUS
CONDITIONS BE AWARE OF THE DANGERS AND
CONTACT APPROPRIATE PERSONNEL OR CERTIFIED
TECHNICIANS TO SERVICE THE EQUIPMENT
Pressing the alarm button enters the Alarms menu If there
is an Alarm present, the displayed Alarm will look similar to
this example showing time and date of occurrence Press
the
Alarms 0 1 / 0 1
15:35 04/05/17
Comp 1 Low Pressure
If there are no present alarms the NO ALARMS will be
displayed Pressing the enter button with No Alarms
present will enter the Alarm Log The alarm log simply is
a record of the alarms that occurred A total of 64 previous
alarms will be stored into memory If there are no alarm logs
present, the system will not enter the Alarm Logger Press
the Esc button to return to the main status loop
NO ALARMS
Press ENTER to
enter ALARM LOGS
Alarm Logger Record>01
15:35 04/05/17
Comp 2 Low Pressure
Changing Set Points, Parameters, And
Values
Set points, Parameters, and changeable values are known
as Fields Press the enter button to move the cursor to
the field for the desired change. Press the (up) or
(down) button to change the value within that field, and then
press the enter button to save the change into memory
System Status
By default the system remains within the System Status
menu loop if no one has accessed the unit for greater than
five (5) minutes. Simply pressing the (up) or (down)
buttons, scrolls through the available screens within the
System Status menu Each screen in the Status menu
displays the operating conditions or Status of the system
Listed below are the Screens that will appear under System
Status for particular setups based on application setup and
available options
U01 Mon 07:21 03/19/17
Return Hum >
55.0%
Return Temp>
74.7 °F
Supply Temp>
57.2 °F
One Compressor ON